Dometic 57908.521 Скачать руководство пользователя страница 7

7

4.

4.

4.

4.

4.  AIR DISTRIB

 AIR DISTRIB

 AIR DISTRIB

 AIR DISTRIB

 AIR DISTRIBUTION SYSTEM

UTION SYSTEM

UTION SYSTEM

UTION SYSTEM

UTION SYSTEM

INST

INST

INST

INST

INSTALLA

ALLA

ALLA

ALLA

ALLATION

TION

TION

TION

TION

The Dometic Corporation recommends the basic con-
figuration shown below for installing this Air Conditioner
System. We have found by testing, that this configuration
works best in most applications of this Air Conditioner
System.

It is the responsibility of the Installer of this System to
review each RV floor plan and determine the following:

A. Duct size
B. Duct layout
C. Register size
D. Register locations
E. Thermostat location.

These items must be determined in conjunction with the
Air Distribution System Sizing and Design Requirements
listed in Section 3 of this manual.

ALTERNATE CONFIGURATIONS AND METHODS
MAY BE USED WHICH STILL ALLOW THE AIR
CONDITIONER TO OPERATE PROPERLY. HOW-
EVER, THESE ALTERNATE CONFIGURATIONS
AND METHODS MUST BE APPROVED BY THE
DOMETIC CORPORATION IN WRITING.

The following instructions are based upon the use of

The following instructions are based upon the use of

The following instructions are based upon the use of

The following instructions are based upon the use of

The following instructions are based upon the use of
Dometic Return Air Kit No. 3105007 or 3105935

Dometic Return Air Kit No. 3105007 or 3105935

Dometic Return Air Kit No. 3105007 or 3105935

Dometic Return Air Kit No. 3105007 or 3105935

Dometic Return Air Kit No. 3105007 or 3105935. The
electronic kit has mounting bolts supplied for use with this
Kit.

A.

A.

A.

A.

A. Before preparing the ceiling opening, the type of

system options must be decided upon. If a remote
sensor is to be used, provision must be made for it.
If the load shed option is to be used, wires must be run
from the load shed control to the Dometic A/C. If a
furnace is to be connected, wires must be run from
the furnace to the Dometic A/C. Read all of the

Read all of the

Read all of the

Read all of the

Read all of the

following instructions before beginning the in-

following instructions before beginning the in-

following instructions before beginning the in-

following instructions before beginning the in-

following instructions before beginning the in-
stallation

stallation

stallation

stallation

stallation.

B.

B.

B.

B.

B. ROOF AND CEILING OPENING PREPARATION

ROOF AND CEILING OPENING PREPARATION

ROOF AND CEILING OPENING PREPARATION

ROOF AND CEILING OPENING PREPARATION

ROOF AND CEILING OPENING PREPARATION
1) A 14" x 14" opening must be cut through the roof

and ceiling of the RV. This opening must be
located between the roof and reinforcing mem-
bers.

THERE MAY BE ELECTRICAL WIRING BETWEEN

THERE MAY BE ELECTRICAL WIRING BETWEEN

THERE MAY BE ELECTRICAL WIRING BETWEEN

THERE MAY BE ELECTRICAL WIRING BETWEEN

THERE MAY BE ELECTRICAL WIRING BETWEEN
THE ROOF AND THE CEILING. DISCONNECT ALL

THE ROOF AND THE CEILING. DISCONNECT ALL

THE ROOF AND THE CEILING. DISCONNECT ALL

THE ROOF AND THE CEILING. DISCONNECT ALL

THE ROOF AND THE CEILING. DISCONNECT ALL
POWER SUPPLIES AND THE POSITIVE (+ ) TERMI-

POWER SUPPLIES AND THE POSITIVE (+ ) TERMI-

POWER SUPPLIES AND THE POSITIVE (+ ) TERMI-

POWER SUPPLIES AND THE POSITIVE (+ ) TERMI-

POWER SUPPLIES AND THE POSITIVE (+ ) TERMI-
NAL FROM THE SUPPLY BATTERY. FAILURE TO

NAL FROM THE SUPPLY BATTERY. FAILURE TO

NAL FROM THE SUPPLY BATTERY. FAILURE TO

NAL FROM THE SUPPLY BATTERY. FAILURE TO

NAL FROM THE SUPPLY BATTERY. FAILURE TO
FOLLOW THIS INSTRUCTION MAY CREATE A SHOCK

FOLLOW THIS INSTRUCTION MAY CREATE A SHOCK

FOLLOW THIS INSTRUCTION MAY CREATE A SHOCK

FOLLOW THIS INSTRUCTION MAY CREATE A SHOCK

FOLLOW THIS INSTRUCTION MAY CREATE A SHOCK
HAZARD.

HAZARD.

HAZARD.

HAZARD.

HAZARD.

2) Mark a 14" x 14" square on the roof and carefully

cut the opening.

3)

Using the roof opening as a guide, cut the
matching hole in the ceiling.

4)

The opening created must be framed to provide
adequate support and prevent air from being
drawn from the roof cavity. Lumber 3/4" or more in
thickness must be used. Remember to provide an
entrance hole for power supplies, furnace wiring,
4-conductor telephone cable, remote sensing and
load shed options as desired.

5)

The 14" opening is part of the return air system of
the Air Conditioner and must be finished in accor-
dance with NFPA Standard 501C Section 2.7.

6)

Route a copper 12 AWG, with ground, 115 VAC
supply line from the fuse or circuit breaker box to
the roof opening.

a. This supply line must be located in the front

portion of the 14" opening.

b. The power supply MUST

MUST

MUST

MUST

MUST be on a separate 20

amp Time Delay Fuse or HACR Circuit Breaker.

c. Make sure at least 15" of supply wire extends

into the roof opening. This ensures easy con-
nection at the Junction Box.

d. Wiring must comply with all National, State and

Local Wiring Codes.

e. Use a steel sleeve and a grommet or equivalent

methods to protect the wire where it passes into
the opening.

7)

Route a dedicated 12 VDC supply line (18-22
AWG) from the RV's Converter or Battery to the
roof opening.

a. This supply line must be located in the front

portion of the 14" opening.

b. Make sure that at least 15" of supply wire

extends into the roof opening.

c. In a multiple zone installation, this wiring is

In a multiple zone installation, this wiring is

In a multiple zone installation, this wiring is

In a multiple zone installation, this wiring is

In a multiple zone installation, this wiring is
required in only one of the 14" openings

required in only one of the 14" openings

required in only one of the 14" openings

required in only one of the 14" openings

required in only one of the 14" openings.

8)

If a Remote Temperature Sensor is to be used
(Part No. 3106486.008), the connector end must
be routed to the roof opening of the system which
is till control. Make sure that at least 15" of the
sensor cable extends into the roof opening. Mount
the Remote Sensor in a location 54" above the
floor and away from any heat source in the area
that is to be controlled.

9)

If a furnace is to be controlled by the system, the
two furnace thermostat leads must be routed to
the roof opening of the air conditioner that will
control it. Make sure at least 15" of the furnace
thermostat wires extend into the roof opening.

10) If an Energy Management System (EMS) is to be

used with the control, two wires must be routed to
the roof opening of the zone to be managed. The
signal required for this function is a normally open
relay contact. When the EMS calls for the com-
pressor to shut off, the relay contacts should
close. Make sure that at least 15" of the EMS wires
extend into the roof opening.

Содержание 57908.521

Страница 1: ...aide ou des obtenir de l aide ou des obtenir de l aide ou des reseignements compl mentaires reseignements compl mentaires reseignements compl mentaires reseignements compl mentaires reseignements com...

Страница 2: ...the ceiling windows metal parts etc The air conditioner removes this moisture from the air during normal operation Keeping doors and windows closed when this air conditioner is in opera tion will mini...

Страница 3: ...e ZONE 1 ZONE 1 ZONE 1 ZONE 1 ZONE 1 2 2 2 2 2 3 3 3 3 3 or 4 4 4 4 4 2 The mode of operation is selected by momentarily depressing the MODE MODE MODE MODE MODE pushbutton 3 The fan speed is selected...

Страница 4: ...ter in place This may plug the unit evaporator coil filter in place This may plug the unit evaporator coil filter in place This may plug the unit evaporator coil filter in place This may plug the unit...

Страница 5: ...ing these instructions C Installation must comply with the National Electrical Code and any State or Local Codes or regulations D DO NOT add any devices or accessories to this air conditioner except t...

Страница 6: ...the Air Conditioner NOTE NOTE NOTE NOTE NOTE THE DOMETIC CORPORATION WILL NOT BE HELD THE DOMETIC CORPORATION WILL NOT BE HELD THE DOMETIC CORPORATION WILL NOT BE HELD THE DOMETIC CORPORATION WILL NO...

Страница 7: ...LIES AND THE POSITIVE TERMI POWER SUPPLIES AND THE POSITIVE TERMI NAL FROM THE SUPPLY BATTERY FAILURE TO NAL FROM THE SUPPLY BATTERY FAILURE TO NAL FROM THE SUPPLY BATTERY FAILURE TO NAL FROM THE SUPP...

Страница 8: ...ve the floor b Install the Comfort Control Center on a partition not on an outside wall FRAME 14 OP ENING AC P OWER SUPPLY W IRE DUCT FRAME FRAME THERMOSTAT CA BLE DUCT ROOF INSULATION DUCT T O REA R...

Страница 9: ...air opening of the Air Conditioner and pull the unit electrical cord down for later connection C C C C C COMFORT CONTROL CENTER INSTAL COMFORT CONTROL CENTER INSTAL COMFORT CONTROL CENTER INSTAL COMFO...

Страница 10: ...LATE INSTALLATION OF DIVIDER PLATE INSTALLATION OF DIVIDER PLATE INSTALLATION OF DIVIDER PLATE 1 Measure the ceiling to roof thickness a If distance is 2 00 3 75 remove perforated tab from Divider Pla...

Страница 11: ...s approved for use on 590 Series Air Conditioners only Follow the instructions with the heat package for only Follow the instructions with the heat package for only Follow the instructions with the he...

Страница 12: ...ntrol Bo Electronic Control Box The polarity of these connections does not matter 4 Connect the previously run Energy Management System wires if applicable to the yellow wires protruding from the Elec...

Страница 13: ...configuration I I I I I INSTALLATION OF RETURN AIR COVER INSTALLATION OF RETURN AIR COVER INSTALLATION OF RETURN AIR COVER INSTALLATION OF RETURN AIR COVER INSTALLATION OF RETURN AIR COVER 1 Remove R...

Страница 14: ...ING DIAGRAM UNIT FIELD WIRING DIAGRAM UNIT FIELD WIRING DIAGRAM UNIT FIELD WIRING DIAGRAM UNIT FIELD WIRING DIAGRAM UNIT FIELD WIRING DIAGRAM RED BLU 3105052 009 RED BLK YEL RED GRN YEL GRN YEL WHT WH...

Отзывы: