INSTALLATION INSTRUCTIONS DUCTED  CCC

5. AIR DISTRIBUTION SYSTEM INSTALLATION

A. Dometic Corporation recommends the basic configuration shown on page 8 for installing this air conditioner/heat pump

system. We have found through testing that this configuration works best in most applications of this air conditioner/heat pump
system. It is the responsibility of the Installer of this system to review each RV floor plan and determine the following:
1. Duct size
2. Duct layout
3

Register size

4. Register location
5. Thermostat location
These items must be determined in conjunction with the Air Distribution System and Sizing and Design Requirements listed
in the chart on page 5.

Important: 

Alternate configurations and methods may be used which still allow the air conditioner/heat pump

to operate properly; however, these alternate configurations and methods must be approved by the Dometic
Corporation in writing. The following instructions are based upon the use of Dometic  3105007.XXX Return Air Kits,
3105935.XXX Quick Cool Kits,  or 3308120.XXX Genesis Air Filtration System. The 3109226.XXX and 3109407.XXX
Comfort Control Center Kits have the mounting bolts supplied for use with these kits.

B. ROOF AND CEILING OPENING PREPARATION

1. A 14-1/4" x 14-1/4" (±1/8") opening must be cut through the roof and ceiling of the RV. This opening must  be  located

between the roof reinforcing members.

There may be electrical wiring between the
roof and the ceiling. Disconnect 115 volt AC
power cord and the positive (+) 12 volt DC
terminal at the supply battery. Failure to fol-
low this instruction may create a shock haz-
ard causing death or severe personal injury.

2. Mark a 14-1/4" x 14-1/4" (±1/8") square on the roof and carefully cut the opening.
3. Using the roof opening as a guide, cut the matching hole in the ceiling.
4. The opening created must be framed to provide adequate support and prevent air from being drawn from the roof cavity.

Lumber 3/4" or more in thickness must be used. Remember to provide an entrance hole for power supply wiring and
thermostat cable.

5. The 14-1/4" x 14-1/4" (±1/8") opening is part of the return air system of the air conditioner/heat pump and must be finished

in accordance with NFPA Standard 501C Section 2.7.

6. Route a copper 12 AWG (max. length 24'), with ground, supply line from the fuse or circuit breaker box to the roof opening.

a. This supply line must be located in the front portion of the 14-1/4" x 14-1/4" (±1/8") opening.
b. The power supply MUST be on a separate 20 amp for models 579, 590, 591,59516, 600 and 630 series, and 15 amp

for models 59528, 59529 and 59530 Series Time Delay Fuse or HACR Circuit Breaker.

c. Make sure at least 15" of supply wire extends into the roof opening. This ensures easy connection at the junction

box.

d. Wiring must comply with all National, State and Local Wiring Codes.
e. Use a steel sleeve and a grommet or equivalent methods to protect the wire where it passes into the opening.

7.

See Section 6. Comfort Control Center, Remote Sensor and Cable Installation.

WARNING

!

Содержание 57908.321

Страница 1: ...ic Control Kit Ducted 59136 531 59136 536 59136 621 59136 631 59516 303 59516 331 59516 336 59516 501 59516 531 59516 536 59516 601 59530 632 600312 321 600315 326 600312 421 600315 321 600315 421 630...

Страница 2: ...erature For a more permanent solution to high heat gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy compa...

Страница 3: ...1 3 62 0 2 5 5 8 325 250 0 55 0 90 16 0 20 Amp 94 3 5 KW 5 0 KW 57915 621 13 500 11 0 54 4 2 5 5 8 325 250 0 55 0 90 16 0 20 Amp 94 3 5 KW 5 0 KW 57915 622 13 500 11 0 54 4 2 5 5 8 325 250 0 55 0 90 1...

Страница 4: ...31 N A 8 0 48 3 2 0 5 6 325 250 0 40 1 10 19 0 15 Amp 94 3 5 KW 5 0 KW 59530 531 N A 7 8 53 0 2 0 5 6 325 250 0 40 1 10 19 0 15 Amp 94 3 5 KW 5 0 KW 59530 532 N A 8 0 53 0 2 5 5 8 325 250 0 40 1 10 18...

Страница 5: ...front to back and centered from side to side B For Two Unit Installations Install one air conditioner heat pump one third and one airconditioner heatpumptwo thirdsfromfrontofRVand centered from side t...

Страница 6: ...ductwork will not collapse or bend during and after the installation Dometic Corporation will not be liable for roof struc tural or ceiling damage due to improperly in sulated sealed or collapsed duc...

Страница 7: ...be electrical wiring between the roof and the ceiling Disconnect 115 volt AC power cord and the positive 12 volt DC terminal at the supply battery Failure to fol low this instruction may create a sho...

Страница 8: ...Duct Size And Requirements For 3105007 XXX And 3105935 XXX Return Air Cover Duct Size And Requirements For 3308120 XXX Genesis Air Filtration System Total Outlet Air Area Minimum 21 0 Sq In Total Outl...

Страница 9: ...dedicated 12VDC supply line 18 to 22 AWG from the RV s converter or battery to the roof opening a This supply line must be located in the front portion of the 14 1 4 x 14 1 4 1 8 opening b Make sure t...

Страница 10: ...V AC REAR A C 115V AC REAR A C 4 CONDUCTOR CONTROL CABLE 4 CONDUCTOR CONTROL CABLE 115V AC FRONT A C 115V AC FRONT A C FURNACE 2 WIRES FURNACE 2 WIRES DOMETIC COMFORT CONTROL CENTER DOMETIC COMFORT CO...

Страница 11: ...f the air conditioner and pull the unit electrical cord down for later installation See FIG 11 AC Power Supply Pull Electrical Cord Down Roof Gasket FIG 11 Disconnect 115 volt AC Failure to follow the...

Страница 12: ...nterTM CCC cable previously terminated see Section 6 B Control Cable into one of the control cable leads out of the air conditioner Either one of the two 2 control cables can be used 6 Connect the rem...

Страница 13: ...sive The foam divider should be level with the ceiling 1 4 Tear off the excess at the pre cut perforations in divider See FIG 13B 2 Peel the paper off of the foam divider and stick it in place on the...

Страница 14: ...ed See FIG 16B for Brisk Air unit and Fig 17B for Penguin units FIG 15A Installing unit with 3308120 XXX Genesis Air Filtration System continued on page 15 column B FIG 16A If bolts are left loose the...

Страница 15: ...luminum foil tape not supplied to seal the ends of the foam divider to the sides of the opening Make sure the area behind the flange on the ceiling template is sealed See FIG 18B FIG 18B Use Aluminum...

Страница 16: ...t power be supplied to the air conditioner and check for proper operation Refer to Operating Manual or User s Guide for a description of the air conditioner operation Installing unit with 3308120 XXX...

Страница 17: ...e shortened by placing the Differential dip switch in the ON position Note Setting the Differential dip switch should only be required when the installation conditions are less than desirable and is n...

Страница 18: ...579 590 591 595 600 630 579 590 591 595 600 630 509 S POPLAR ST 509 S POPLAR ST LAGRANGE IN 46761 LAGRANGE IN 46761 115VAC 60Hz 1 O 115VAC 60Hz 1 O 60 HZ 1 O 60 HZ 1 O 3106515 020 USE COPPER USE COPPE...

Отзывы: