Dometic 57908.321 Скачать руководство пользователя страница 17

17

INSTALLATION INSTRUCTIONS DUCTED  CCC

10. SYSTEM CONFIGURATION, RESET & CHECKOUT

A. ELECTRONIC CONTROL CONFIGURATION

Depending on the equipment options installed by the recreational vehicle manufacturer, the appropriate dip switches will need
to be switched to the "ON" position. See Fig. 20. Placing the switch in the "ON" position selects that option.
Note: Dip switches are in the "OFF" position when shipped from the factory.

1.

Zone selection - when two or more units are installed and controlled by one Comfort  Control Center

TM

, the second unit

becomes Zone 2, the third unit Zone 3, and the fourth unit Zone 4. The appropriate zone dip switch must be set in each
electronic control box for the Zone 2, 3 and 4. See FIG. 20.

2.

Heat Strip selection - For units with a heat strip push the #1 dip switch to the "ON" position.  See FIG. 20.

3.

Heat pump models must have the red plug of the outdoor ambient sensor plugged into the RED (P3) plug.

4.

Furnace selection - when a furnace has been connected to a zone, place the furnace dip switch "ON" for that zone.

5.

Differential - differential is the temperature difference between the "ON/OFF" cycle of the thermostat. The normal
differential is preset in the circuit board with the dip switch set to the "OFF" position. In some situations, it may be
necessary to decrease the Differential. The location of the thermostat may create a condition where the normal Differential
will not maintain your comfort zone. If this occurs, the Differential can be shortened by placing the Differential dip switch
in the "ON" position.

Note: Setting the Differential dip switch should only be required when the installation conditions are less than desirable and
is not covered under the limited warranty.

6.

STAGE is not used on these units. Leave in the "OFF" position.

7.

Gen start selection - leave in the "OFF" position.

8.

Replace the unit electrical box cover.

9.

Replace the return air cover.

10. Repeat this procedure for each additional zone.

B. SYSTEM RESET
After setting the dip switches in the electric box, do a system reset. See FIG. 21.

1.

Turn the ON/OFF switch to the "OFF" position.

2.

Simultaneously Depress and hold the MODE and ZONE push-buttons while turning the ON/OFF switch to "ON". FF

should appear in the LCD display until the MODE and ZONE push-buttons are released.

3.

When a dip switch is turned on or off after initial configuration, a system reset will need to be done before the Comfort

Control Center

TM

 will recognize the updated selection.

C. SYSTEM CHECKOUT
Verify that all features of the installed system work. Check fan speeds, cooling mode, heat pump mode, furnace (if con-
nected) and heat strip. If the features do not work, check all wiring and confirm that the correct options have been selected
on the Electronic Control Board. See Comfort Control Center™ Operating Instructions.

FIG. 20

1 2 3 4 5

HEA

TST

RIP

ZO

NE

2

ZO

NE

3

ZO

NE

4

FU

RN

AC

E

DIP
SWITCHES

DIP
SWITCHES

ON

6 7 8

D

IFFEREN

TIAL

ST

AGE

GEN

ST

ART

Mode Push-Button

Fan Push-Button

Up Push-Button

Down Push-Button

Zone Push-Button

MO

DE

MO

DE

FAN

FAN

UP

UP

DO

WN

DO

WN

OFF

ON

OFF

ON

ZO

NE

ZO

NE

TEM

P

TEM

P

ON/OFF Switch

FIG. 21

Содержание 57908.321

Страница 1: ...ic Control Kit Ducted 59136 531 59136 536 59136 621 59136 631 59516 303 59516 331 59516 336 59516 501 59516 531 59516 536 59516 601 59530 632 600312 321 600315 326 600312 421 600315 321 600315 421 630...

Страница 2: ...erature For a more permanent solution to high heat gain accesso ries like A E outdoor patio and window awnings will reduce heat gain by removing the direct sun They also add a nice area to enjoy compa...

Страница 3: ...1 3 62 0 2 5 5 8 325 250 0 55 0 90 16 0 20 Amp 94 3 5 KW 5 0 KW 57915 621 13 500 11 0 54 4 2 5 5 8 325 250 0 55 0 90 16 0 20 Amp 94 3 5 KW 5 0 KW 57915 622 13 500 11 0 54 4 2 5 5 8 325 250 0 55 0 90 1...

Страница 4: ...31 N A 8 0 48 3 2 0 5 6 325 250 0 40 1 10 19 0 15 Amp 94 3 5 KW 5 0 KW 59530 531 N A 7 8 53 0 2 0 5 6 325 250 0 40 1 10 19 0 15 Amp 94 3 5 KW 5 0 KW 59530 532 N A 8 0 53 0 2 5 5 8 325 250 0 40 1 10 18...

Страница 5: ...front to back and centered from side to side B For Two Unit Installations Install one air conditioner heat pump one third and one airconditioner heatpumptwo thirdsfromfrontofRVand centered from side t...

Страница 6: ...ductwork will not collapse or bend during and after the installation Dometic Corporation will not be liable for roof struc tural or ceiling damage due to improperly in sulated sealed or collapsed duc...

Страница 7: ...be electrical wiring between the roof and the ceiling Disconnect 115 volt AC power cord and the positive 12 volt DC terminal at the supply battery Failure to fol low this instruction may create a sho...

Страница 8: ...Duct Size And Requirements For 3105007 XXX And 3105935 XXX Return Air Cover Duct Size And Requirements For 3308120 XXX Genesis Air Filtration System Total Outlet Air Area Minimum 21 0 Sq In Total Outl...

Страница 9: ...dedicated 12VDC supply line 18 to 22 AWG from the RV s converter or battery to the roof opening a This supply line must be located in the front portion of the 14 1 4 x 14 1 4 1 8 opening b Make sure t...

Страница 10: ...V AC REAR A C 115V AC REAR A C 4 CONDUCTOR CONTROL CABLE 4 CONDUCTOR CONTROL CABLE 115V AC FRONT A C 115V AC FRONT A C FURNACE 2 WIRES FURNACE 2 WIRES DOMETIC COMFORT CONTROL CENTER DOMETIC COMFORT CO...

Страница 11: ...f the air conditioner and pull the unit electrical cord down for later installation See FIG 11 AC Power Supply Pull Electrical Cord Down Roof Gasket FIG 11 Disconnect 115 volt AC Failure to follow the...

Страница 12: ...nterTM CCC cable previously terminated see Section 6 B Control Cable into one of the control cable leads out of the air conditioner Either one of the two 2 control cables can be used 6 Connect the rem...

Страница 13: ...sive The foam divider should be level with the ceiling 1 4 Tear off the excess at the pre cut perforations in divider See FIG 13B 2 Peel the paper off of the foam divider and stick it in place on the...

Страница 14: ...ed See FIG 16B for Brisk Air unit and Fig 17B for Penguin units FIG 15A Installing unit with 3308120 XXX Genesis Air Filtration System continued on page 15 column B FIG 16A If bolts are left loose the...

Страница 15: ...luminum foil tape not supplied to seal the ends of the foam divider to the sides of the opening Make sure the area behind the flange on the ceiling template is sealed See FIG 18B FIG 18B Use Aluminum...

Страница 16: ...t power be supplied to the air conditioner and check for proper operation Refer to Operating Manual or User s Guide for a description of the air conditioner operation Installing unit with 3308120 XXX...

Страница 17: ...e shortened by placing the Differential dip switch in the ON position Note Setting the Differential dip switch should only be required when the installation conditions are less than desirable and is n...

Страница 18: ...579 590 591 595 600 630 579 590 591 595 600 630 509 S POPLAR ST 509 S POPLAR ST LAGRANGE IN 46761 LAGRANGE IN 46761 115VAC 60Hz 1 O 115VAC 60Hz 1 O 60 HZ 1 O 60 HZ 1 O 3106515 020 USE COPPER USE COPPE...

Отзывы: