Electronic duct air flow sensor
RHEASGARD
®
KLGF
with active output, in an impact-resistant plastic housing, optionally with ⁄ without display, for
determining the flow velocity in m/s. The measuring transducer converts the measurement signal into a standard signal of 0 - 10 V.
Electronic duct air flow monitor
RHEASREG
®
KLSW
with switching output (relay one-step or two-step), in a plastic housing, for determining the flow
velocity in m/s. Fine adjustment of the measuring range end value by the user is possible with the help of a potentiometer. The flow sensors are
suitable for monitoring or controlling airflows in ducts, at ventilators and dampers, for flow-dependent monitoring of humidifiers and electric heating
registers according to DIN 57100, part 420, or for use in connection with DDC systems.
TECHNICAL DATA
Power supply:
24 V AC ⁄ DC or
230 V AC +5 ⁄ –13 %, 50...60 Hz
Output:
1 or 2 potential-free relays (changeover contacts), 8 A, max. 2 kW or
0 - 10 V (relative, linearised on request), see table
Current consumption:
approx. 3 VA
KLGF -1, KLSW- 3, KLSW- 4
KLSW - 6
Measuring range:
0.1...30 m/s
0.1...15 m/s
Sensitivity:
0.1...30 m/s
(adjustable)
0.1...15 m/s
(adjustable)
Switching hysteresis:
2 % (permanently set)
approx. 1...10 %
(adjustable)
Start bridging:
–
approx. 15...120 s
(adjustable)
Switch-off delay:
–
approx. 2...20 s
(adjustable)
Connection cable:
max. 50 m at minimum cross section 1.5 mm
2
per conductor;
avoid laying parallel with mains voltage-carrying lines,
or use shielded cables, apply cable screen one-sided
Ambient temperature:
0...+60 °C at the device; 0...+80 °C medium
Medium:
pollutant-free, non-precipitating air
Sensor:
sensor breakage protection, temperature-compensated
Housing:
plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced,
colour traffic white (similar to RAL 9016)
KLSW-xx, KLGF -1 with display:
108 x 70 x 73.5 mm (Thor 2)
KLGF -1 without display:
72 x 64 x 37.8 mm (Tyr 1), with quick-locking screws (slotted ⁄ Phillips head combination)
Cable gland:
M 16 x 1.5; including strain relief, exchangeable, max. inner diameter 10.4 mm
Protective tube:
metal (brass, nickel-plated), Ø 10 mm, nominal length NL = 140 mm
Process connection:
by mounting flange (included in the scope of delivery)
Electrical connection:
0.25 - 2.5 mm
2
, via screw terminals
Protection class:
II (according to EN 60 730) at KLSW 3 (UB = 230 V AC)
III (according to EN 60 730) at UB = 24 V
Protection type:
IP 65
(according to EN 60 529)
Standards:
CE conformity, EMC directive 2014 ⁄ 30 ⁄ EU, low-voltage directive 2014 ⁄ 35 ⁄ EU
RHEASGARD
®
KLGF
Duct airflow monitors
RHEASREG
®
KLSW
Duct airflow monitors, one-step and two-step
Type ⁄ WG01
Relay
(Steps)
Power-
Supply
Output
Display Item No.
KLGF
K LGF 1
–
24 V AC ⁄ DC
0 -10 V (relative)
1701-3120-1000-000
K LGF 1_ Display
–
24 V DC
0 -10 V (linearised)
■
on request
KLSW
one-step
K L S W 3
1
230 V AC
1 x Changeover contact
1701-3011-0001-000
K L S W 4
1
24 V AC ⁄ DC
1 x Changeover contact
1701-3021-0000-000
KLSW
two-step
K L S W 6
2
24 V AC ⁄ DC
2 x Changeover contact
1701-3022-0000-000
Note:
KLSW 6
is supplied as standard with a
manual reset button
!
Automatic reset
(without reset button)
on request