G
RHEASREG
®
KLSW 3 ⁄ KLSW 4
Series KLSW electronic airflow monitors are used for monitoring ventilators and dampers, for flow-dependent monitoring of humidifiers
and electric heating registers according to DIN 57100, part 420, or for applications in connection with DDC systems. Function: After
applying operating voltage (green LED lighting) and building up the desired flow velocity (red LED lighting) within the starting delay,
the »Alarm« relay is activated and the subsequent device is released. Sometimes detrimental heating ⁄ humidifying without air discharge
is so avoided. In case the necessary airspeed is not reached within the starting delay, the »Alarm« relay drops out. Contacts 12 ⁄ 11
close. When preset flow rate is reached again, the »Alarm« relay is reactivated. Contacts 11 ⁄ 14 close. By pressing the Reset button,
the device is reset to its initial condition.
TECHNICAL DATA
Type
KLSW 4
KLSW 3
Item No.
Operating voltage
24V AC ⁄ DC
230 V ⁄ AC
Voltage tolerance
± 10%
± 10%
Overvoltage category
II
II
Signal indication, voltage
green LED
green LED
Power consumption max.
2 VA
4 VA
Device ambient temperature
–20..+60 °C
–20..+60 °C
Signal output flow
1 changeover contact
1 changeover contact
Current ⁄ contact load
250 V AC, 6 A, 1.5 kVA
250 V AC, 6 A, 1.5 kVA
Switching function at flow
relay activated
relay activated
Signal indication at flow
yellow LED
yellow LED
Start bridging
60 s (via jumper)
60 s (via jumper)
Start bridging indication
yellow LED
yellow LED
Media temperature range
–10..+80 °C
–10..+80 °C
Temperature gradient
15 K ⁄ min
15 K ⁄ min
Switchpoint
adjustable via potentiometer
adjustable via potentiometer
Measuring range
0.1 - 30 m ⁄ s
0.1 - 30 m ⁄ s
Response time
1...10 s
1...10 s
Measuring sensor
built-in
built-in
Immersion depth
130 mm
130 mm
Process connection
PG7, mounting flange
PG7, mounting flange
Sensor material
MS 58, nickel -plated
MS 58, nickel -plated
Pressure resistance
10 bar
10 bar
Connection
5 terminals, 2.5 mm
2
5 terminals, 2.5 mm
2
Protection type, housing
IP 65
IP 65
Protection type, sensor
IP 67
IP 67
Contamination class
2
2
Housing dimensions
108 x 70 x 73.5 mm (Thor II)
108 x 70 x 73.5 mm (Thor II)
Test mark
0
0
Accessories (included)
mounting flange 10 mm
mounting flange 10 mm
Start bridging
Jumper plugged
= start bridging active for ca. 60 s, yellow LED »Time« lighting
Jumper not plugged
= start bridging inactive