MODBUS
FC013 Fancoil controller
Release 18.12.2014 ver. 01900
set night/ pre-
comfort heating
temp
16 LSB
16 MSB
R,W
EEPROM
night/standby mode heating
temperature setpoint
set by user
(default = 19
C, 0x076C)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
set depression/
economy heating
temp
17 LSB
17 MSB
R,W
EEPROM
off mode heating temperature
setpoint
set by user
(default = 12
C, 0x04B0)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
set day/ comfort
cooling temp
18 LSB
18 MSB
R,W
EEPROM
day/comfort mode cooling
temperature setpoint
set by user
(default = 24
C, 0x0960)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
set night/ pre-
comfort cooling
temp
19 LSB
19 MSB
R,W
EEPROM
night/standby mode cooling
temperature setpoint
set by user
(default = 26
C, 0x0A28)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
set depression/
economy cooling
temp
20 LSB
20 MSB
R,W
EEPROM
off mode cooling temperature
setpoint
set by user
(default = 35
C, 0x0DAC)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
actual temp
21 LSB
21 MSB
R, RAM
actual temperature measured by
the internal sensor incl. correction
(see
temp sensor corr
)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex