background image

 

MODBUS  

FC013 Fancoil controller 

Release 18.12.2014 ver. 01900

 

 

baud rate  

4 MSB 

R,W 
EEPROM 
(9600 bps, 
13dec) 

communication speed 
10

dec

 

… 1 200 bps 

11

dec

 

… 2 400 bps 

12

dec

 

… 4 800 bps 

13

dec

 

… 9 600 bps (default) 

14

dec

 

… 19 200 bps 

15

dec

 

… 38 400 bps 

16

dec

 

… 57 600 bps 

17

dec

 

… 115 200 bps 

!!!

 the change will be 

effective after restart only 
(however the register will 
be set immediately) 

serial port 
settings 

5 LSB 

R,W 
EEPROM 
(no parity, 
one stop bit, 
0x00) 

serial line parameter settings 
 
(default = no parity, 1 stop bit) 

bit 0-1 ... parity (00 

– no 

parity, 01 

– even, 10 – 

odd) 
bit 2 ... stop bits (0 

– one, 

1 - two) 

!!!

 the change will be 

effective after restart only 
(however the register will 
be set immediately) 

 

5 MSB 

 

reserved 

 

EEPROM writes  6 LSB 

6 MSB 

R, EEPROM 

number of EEPROM writing 
cycles, does not overflow, cannot 
be reset by INIT nor by any other 
means 

 

relay 

7 LSB 

R, RAM 

output relay status (DO1-DO2) -  
copy of the AO1 and AO2 outputs 

bit 0 ... relay 1, heating 
bit 1 ... relay 2, cooling 

inputs 

7 MSB 
 

R, RAM 

digital input status (DI1 ... 
presence, DI2 ... window / alarm 
contact). The DI status respects 
the NO/NC settings in 

inputs 

settings

 register. Slave controllers 

are taken into account if the inputs 
are enabled for controls at the 
master module. 

bit 0 ... input(s) DI1 
bit 1 ... input(s) DI2 
bit 2 ... heating demand 
(PID output HEAT > 5%) 
bit 3 ... cooling demand 
(PID output COOL > 5%) 

PID output 
HEAT 

8 LSB 

R, RAM 

heating controller output 

in %, range 0 .. 100% 
(corresponds 0 .. 10 V) 

PID output 
COOL 

8 MSB 

R, RAM 

cooling controller output 
(active also in the change-over 
mode) 

in %, range 0 .. 100% 
(corresponds 0 .. 10 V) 

PID fan speed 

9 LSB 

R, RAM 

fan status as set by the PI

 

controller 

 

in %, range 0 .. 100% 
(corresponds 0 .. 10 V), in 
the comfort mode the 
minimum level is given by 
the 

fan minimum 

register 

UC comm. state  9 MSB 

R, RAM 

communication status of the room 
unit UC 095 (if communication fails 
for 60 secs, all controller outputs 
go to off (except for those 
controlled manually, see register 

manual control

0 ... communication OK 
1 ... timeout 
2 ... MB exception 
3 ... MB error 

Содержание FC013

Страница 1: ... if the INIT switch was ON at power up and if INIT switch was OFF at setting bit 4 to 1 indicated by bit 2 in Status MSB SW reset follows if enabled and 1 is written into the SW reset register address 1002 status MSB 3 MSB R RAM module status upper byte bit 0 0 normal mode 1 init mode bit 1 1 at the next EEPROM write attempt will all data be written to EEPROM 0 at the next EEPROM write attempt wil...

Страница 2: ...O2 outputs bit 0 relay 1 heating bit 1 relay 2 cooling inputs 7 MSB R RAM digital input status DI1 presence DI2 window alarm contact The DI status respects the NO NC settings in inputs settings register Slave controllers are taken into account if the inputs are enabled for controls at the master module bit 0 input s DI1 bit 1 input s DI2 bit 2 heating demand PID output HEAT 5 bit 3 cooling demand ...

Страница 3: ... 11 MSB R W RAM manual cool output setting only if the corresponding bit in the manual control register is set in range 0 100 set temp correction 12 LSB 12 MSB R W RAM setpoint correction set by user resets at each operation mode change 3 5 C reads 350 limits are set in the min and max rel temp correction registers recalculate temperature read value 100 0 0 199 99 19999 0 01 0FFFFhex 199 99 0B1E1h...

Страница 4: ...emperature setpoint set by user default 24 C 0x0960 recalculate temperature read value 100 0 0 199 99 19999 0 01 0FFFFhex 199 99 0B1E1hex set night pre comfort cooling temp 19 LSB 19 MSB R W EEPROM night standby mode cooling temperature setpoint set by user default 26 C 0x0A28 recalculate temperature read value 100 0 0 199 99 19999 0 01 0FFFFhex 199 99 0B1E1hex set depression economy cooling temp ...

Страница 5: ...when residential bit 5 to 14 reserved bit 15 write enable if set to 1 value will be written into register if in 0 attempt will be ignored set fan mode 24 LSB 24 MSB R W EEPROM Fan status set by user the stages correspond to Off 0 Man1 30 Man2 70 Man3 100 If Off AO1 and AO2 are 0 default Auto 0x0001 bit 0 Auto fan A bit 1 Off fan M bit 2 Man 1 fan M Stage1 bit 3 Man 2 fan M Stage1 and 2 bit 4 Man 3...

Страница 6: ...7 valve type 0 NC 1 NO inputs settings inputs enable inputs logic 26 MSB R W EEPROM inputs configuration DI1 presence DI2 window alarm contact default inputs enabled normally open i e active when contact on 0x0F bit 0 DI1 enabled for operation mode control bit 1 DI2 enabled for operation mode control bit 2 DI1 sense 0 NC normally closed 1 NO normally open bit 3 DI2 sense 0 NC normally closed 1 NO ...

Страница 7: ...master the change will be effective after restart only default 0 0 multi slave function is off 1 or above number of FC013 slave modules manual heat digital output 30 LSB R W RAM manual setting of DO1 only if the corresponding bit in manual control set otherwise the output copies the AO1 In manual mode the DO is always a PWM output regardless of reg 29 LSB bit 4 in range 0 100 manual cool digital o...

Страница 8: ... min day night depression temp 35 LSB 35 MSB R W EEPROM minimum temperature which user can set as setpoint for day night and off modes 199 99 to 199 99 default 10 C 0x03E8 recalculate temperature read value 100 0 0 199 99 19999 0 01 0FFFFhex 199 99 0B1E1hex max day night depression temp 36 LSB 36 MSB R W EEPROM maximum temperature which user can set as setpoint for day night and off modes 199 99 t...

Страница 9: ...B R W EEPROM delay between heating valve activation and fan start for heating only prevents circulation of cold air at startup in secs 10 2 20 s 5 50 s show time 42 LSB R W EEPROM time in 100 ms to display each value in show mode default 3 s 0x1E see show mode edit return time 42 MSB R W EEPROM time in secs of user inactivity to return from edit mode to show mode default 30 s 0x1E quick edit mode ...

Страница 10: ...ight moon occupied house bit 2 depression empty house bit 3 auto clock bit 4 party sun drink clock after 2h goes to auto fan mode edit mask 47 LSB 47 MSB R W EEPROM fan states that user is able to switch between default all 0x001F bit 0 Auto fan A bit 1 Off fan M bit 2 Man 1 fan M Stage1 bit 3 Man 2 fan M Stage1 and 2 bit 4 Man 3 fan M Stage1 2 and 3 display symbols 48 LSB 48 MSB R W RAM displayed...

Страница 11: ...W EEPROM time schedule Monday time of event No 3 in mins since 0 00 midnight default 14 00 h 0x0348 e g 121 2h 1min program Monday Event 3 value 59 LSB 59 MSB R W EEPROM time schedule Monday event No 3 value default 0 0x0000 0 day comfort 1 night standby 2 off depression bit 15 1 event is disabled program Monday Event 4 time 60 LSB 60 MSB R W EEPROM time schedule Monday time of event No 4 in mins ...

Страница 12: ...it 15 1 event is disabled uptime 1000 LSB 1000 MSB 1001 LSB 1001 MSB R uptime s number of seconds after last power on reset SW reset 1002 LSB 1002 MSB R W RAM If a non zero value is written and SW reset is enabled see Status LSB bit 1 the device is restarted Real time table Commissioning mode when powered on with pushbutton pushed after several seconds the commissioning mode is activated with manu...

Отзывы: