MODBUS
FC013 Fancoil controller
Release 18.12.2014 ver. 01900
manual control
10 LSB
R, W RAM
manual output control and change-
over (C/O); if a bit is set to 1, the
output goes to state defined below
(see
manual fan speed, manual
heat output, manual cool
output, manual heat digital
output, manual cool digital
output
); if set to 0, PI controller
output values apply, and DO1 and
2 copy the AO1 and 2.
bit 0 ... AO3 - fan
bit 1 ... AO1 - heat output
bit 2 ... AO2 - cool output
bit 3 ... DO1 - heating
bit 4 ... DO2 - cooling
bit 5 ... C/O (1 = active)
manual fan
speed
10 MSB
R, W RAM
manual fan output setting (only if
the corresponding bit in the
manual control
register is set)
in %, range 0 .. 100%
manual heat
output
11 LSB
R, W RAM
manual heat output setting (only if
the corresponding bit in the
manual control
register is set)
in %, range 0 .. 100%
manual cool
output
11 MSB
R, W RAM
manual cool output setting (only if
the corresponding bit in the
manual control
register is set)
in %, range 0 .. 100%
set temp
correction
12 LSB
12 MSB
R, W RAM
setpoint correction set by user;
resets at each operation mode
change
3.5°C reads 350
(limits are set in the
min
and
max
rel. temp correction
registers)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
actual temp set
point HEAT
13 LSB
13 MSB
R, RAM
actual heating setpoint including
setpoint correction (reg. 12)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
actual temp set
point COOL
14 LSB
14 MSB
R, RAM
actual cooling setpoint incl.
setpoint correction (reg. 12)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex
set day/ comfort
heating temp
15 LSB
15 MSB
R,W
EEPROM
day/comfort mode heating
temperature setpoint
set by user
(default = 21
C, 0x0834)
recalculate:
temperature =
read value / 100
0 … 0
199.99 … 19999
-
0.01 … 0FFFFhex
-
199.99 … 0B1E1hex