The product hereby described was developed to perform safety functions 
as a part of a whole installation or machine. A complete safety system 
normally includes sensors, evaluation units, signals and logical modules 
for safe disconnections. The manufacturer of the installation or machine 
is responsible for ensuring proper functioning of the whole system. DOLD  
cannot guarantee all the specifications of an installation or machine that 
was not designed by DOLD. The total concept of the control system into 
which the device is integrated must be validated by the user. DOLD also 
takes over no liability for recommendations which are given or implied in 
the following description. The following description implies no modification 
of the general DOLD terms of delivery, warranty or liability claims.

 

Safety Regulations

-  This device must be installed and operated by trained staff who are  
 

familiar with these instructions and with the current regulations for safety  

  at work and accident prevention.
-  Pay attention to applicable local regulations, especially regarding safety  
 measures.
-  Opening the device or implementing unauthorized changes voids any  
 warranty
-  The unit should be panel mounted in an enclosure rated at IP 54 or  
  superior. Dust and dampness may lead to malfunction.
-  Adequate fuse protection must be provided on all output contacts with  
  capacitive and inductive loads.
-  The safety function must be triggered during commissioning

The input module BG 5913 can only be used with the control unit BH 5911. 
It can extend the number of 2-channels safety inputs up to 13. The Multi-
Function Safety System is used to enable and interrupt a safety circuit in 
a safe way. It can be used to protect people and machines in applications 
with e-stop buttons, safety gates, light curtains with selftesting (Type 4) 
acc. to IEC/EN 61 496-1, 2-hand controls for presses as well as other 
production machinery with dangerous closing action (Type III A or III C to  
EN 574). When used in accordance with its intended purpose and following 
these operating instructions, this device presents no known residual risks. 
Nonobservance may lead to personal injuries and damages to property.

•  According to

 

-

Performance Level (PL) e and category 4 to EN ISO 13849-1: 2008

 

-

SIL Claimed Level (SIL CL) 3 to IEC/EN 62061 

 

-

Safety Integrity Level (SIL 3) to IEC/EN 61508

•  Input module for combination of 3 of the following functions to be set  
  via rotary switch: 

 

- Light curtains (LC) type 4 with manual or automatic start

 

- E-stop 2-channel and manual or automatic start

 

- Two-hand function type IIIC according to DIN/EN 574

•  The functions are selected via rotary switch
•  8 safety inputs
•  2 semiconductor outputs for status indication
•  Broken wire and short circuit monitoring function with error indication
•  LEDs for status indication
•  Width: 22.5 mm

 0272144

Realization of fail-safe control circuits for protection of people and ma-

chinery.

Note:

  This module is intended for applications in which mixed safety 

functions affect one common output.

Further input modules with other combinations of functions are provided 

(e.g. BG 5913.08/_0_ _ _, BG 5913.08/_1_ _ _ , BG 5913.08/_3_ _ _, 

BG 5914.08/_0_ _ _, BH 5914.08/_0_ _ _, BG 5914.08/_1_ _ _,  

BG 5915/_1_ _ _ or BH 5915.08/_1_ _ _).

Green LEDs: 

on, when all inputs are present and start  

 

 

button activated.

White LEDs Run1/
Run 2 and outputs
48 and 58: 

 indicate the current status of the module.

Before installing, operating or maintaining this device, these instructions 
must be carefully read and understood.

Operating instructions                   ENGLISH

Multi-Function Safety System SAFEMASTER M 
Input Module 
BG 5913.08/_3  _ _ _

Translation 

of the original instructions

 

CAUTION

Safe operation of the device is only guaranteed when using certified 
components!

 

DANGER

Dangerous voltage.
Electric shock will result in death or serious injury.

Disconnect all power supplies before servicing equipment.

Important Notes

Designated Use

    

Safety Notes

ATTENTION - AUTOMATIC START!

According to IEC/EN 60 204-1 part 9.2.5.4.2 and 10.8.3 it is not allowed to 
restart automatically after emergency stop. Therefore the machine control 
has to disable the automatic start after emergency stop.

Terminal designation

Signal designation

(-)

Reference potential for 

inputs and outputs

X1, X2

Control outputs

S12, S14, S22, S24

S32, S34, S42, S44

Control inputs

Connection Terminals

Indication

The maximum configuration of the SAFEMASTER M multi-function safety 

system is as follows:

•  the control unit BH 5911

•  up to 3 input modules BG/BH 5913, or BG/BH 5914, BG/BH 5915

•  up to 3 output modules BG 5912

•  1 diagnostic module BG 5551 for CANopen, or

•  1 diagnostic module BG 5552 for Profibus-DP

The BH 5911 controls the whole system.

The input/output modules can be used to expand the control unit in a 

modular way into a multi-functional safety system.

To transmit status messages of the individual modules to a moni to ring or 

control unit, one of the following diagnostic modules may be connected: 

•  BG 5551 for CANopen

•  BH 5552 for Profibus-DP

General Information SAFEMASTER M

Applications

Main Features

All technical data in this list relate to the state at the moment of edition. We reserve the right for 
technical improvements and changes at any time.

Содержание SAFEMASTER M BG 5913.08/ 3 Series

Страница 1: ...n von 3 der folgenden Funktionen Berührungslos wirkende Schutzeinrichtung BWS Typ 4 mit manuellem oder automatischem Start Not Aus 2 kanalig mit manuellem oder automatischem Start Zweihandschaltung Typ IIIC nach DIN EN 574 8 Eingänge für Befehlsgeber 2 Halbleiterausgänge zur Statusanzeige Drahtbruch und Kurzschlussüberwachung mit Fehleranzeige LEDs für Statusanzeigen Baubreite 22 5 mm Realisierung...

Страница 2: ...ich die unbe tätigten Taster nun erneut aktivieren Das Gerät darf gemäß in den Anwendungsbeispielen angeschlossen wer den Durch das Parallel bzw in Reihe Schalten der Bedientasten wird die sichere Funktion der Geräte aufgehoben Die Tasten müssen so beschaffen und angeordnet sein dass sie nicht auf einfache Weise unwirksam gemacht oder unbeabsichtigt betätigt werden können Der Sicherheitsabstand zw...

Страница 3: ...urch Auto Start oder über den Start Taster freigege ben sind der Ausgang 48 und die weiße LED run 1 dauernd aus und der Ausgang 58 dauernd ein Dauernd Aus Blinksignal Dauersignal Ausgang 48 alle Relais inaktiv wegen Systemfehler eine Funktion erteilt keine Freigabe Aktivierung der zugeordneten Sicherheits ausgänge erlaubt LED Run 1 Zweihandschaltung nicht betätigt LED run 2 AN oder alle Relais ina...

Страница 4: ...meine Daten Nennbetriebsart Dauerbetrieb Temperaturbereich 0 50 C Bei einer Betriebstemperatur von 50 C sollte zwischen den Modulen ein Abstand von ca 3 5 mm einge halten werden Luft und Kriechstrecken Bemessungsstoßspannung Verschmutzungsgrad 4 kV 2 Basisisolierung IEC 60 664 1 EMV IEC EN 61 326 3 1 IEC EN 62 061 Funkentstörung Grenzwert Klasse A EN 55 011 Hinweis Dies ist ein Gerät für den Betri...

Страница 5: ...top 2 channel and manual or automatic start Two hand function type IIIC according to DIN EN 574 The functions are selected via rotary switch 8 safety inputs 2 semiconductor outputs for status indication Broken wire and short circuit monitoring function with error indication LEDs for status indication Width 22 5 mm 0272144 Realization of fail safe control circuits for protection of people and ma ch...

Страница 6: ...e connected as specified in the application examples When the operating contacts are connected in parallel or in series safe functioning of the unit is cancelled The two hand buttons must be designed and arranged in such a way as to ensure that they cannot be disabled with easily or pressed unintentionally The safety distance between the push buttons and the place of danger must be large enough to...

Страница 7: ...e white LED Run 1 are permanently OFF and output 58 permanently ON Permanently OFF Pulsing Permanent ON Output 48 all relays inactive due to system error one input function not available Activation of the assigned safety outputs is permissible LED run 1 Two hand control not activated LED run 2 ON or all relays in active due to system error one input function not available LED run 2 ON or system er...

Страница 8: ... Operating mode Continuous operation Temperature range 0 50 C At an operating temperature of 50 C the modules must be mounted with a distance of 3 5 mm Clearance and creepage distances rated impulse voltage pollution degree 4 kV 2 basis insulation IEC 60 664 1 EMC IEC EN 61 326 3 1 IEC EN 62 061 Radio interference suppression Limit value class A EN 55 011 Remark This device is designed for industr...

Страница 9: ...rrières immatérielles EPES type 4 arrêt d urgence 2 canaux avec démarrage automatique ou manuel commande bimanuelle de type IIIC selon DIN EN 574 8 entrées pour émetteurs d ordres 2 sorties à semi conducteurs pour l affichage d état Contrôle de la rupture de conducteur et des courts circuits avec affichage de défaut DEL pour affichages d état Largeur utile 22 5 mm Réalisation de circuits de comman...

Страница 10: ...éclenchement est réactivée et après réappui des BP de la bimanuelle L appareilnedoitêtreraccordéqueselonlesexemplesd utilisationdonnés Le couplage de boutons de commande en parallèle ou en série annule la sécurité de fonctionnement des appareils Les boutons doivent être conçus et disposés de manière à ne pas perdre facilement leur efficacité ou être actionnés de manière intempestive La distance de...

Страница 11: ...e 48 et la DEL jaune run 1 sont coupées en permanence et la sortie 58 alimentée en permanence Arrêt continu Signal clignotant Signal continu Sortie 48 Tous relais inactifs suite à défaut système Une fonction ne donne pas la libération L activation des sorties de sécurité correspondantes est autorisée DEL run 1 Couplage à 2 mains non activé DEL run 2 active ou tous relais inactifs suite à défaut sy...

Страница 12: ...es doit être respectée Distances dans l air et lignes de fuite Catégorie de surtension degré de contamination 4 kV 2 isolation de base IEC 60 664 1 Reyonnement HF 10 V m IEC EN 61 000 4 3 Tensions transitoires sur câbles d alimentation A1 A2 2 kV IEC EN 61 000 4 4 CEM IEC EN 61 326 3 1 IEC EN 62 061 Antiparasitage seuil classe A EN 55 011 Remarque Ceci est un appareil développé pour environement i...

Страница 13: ...o hand 2 NO contact two hand 2 NC contact two hand recognized as operated status 1 two hand not pressed 2 operation of the two buttons correct t 0 5s 3 two hand is pressed 1 2 button 2 has been confirmed too late t 0 5s error status 1 is expected again 4 release of the button is recognized at the first edge at one of the 4 contacts now status 1 is expected 1 2 3 error has been corrected M8989_b em...

Страница 14: ...ulse diagram also apply to the same function in other applications Remarque Les indications de temps d un diagramme sont valables pour la même fonction dans toutes les applications M9188 2 2 2 2 2 2 supply voltage A1 A2 emergency stop 1 S12 S14 emergency stop or LC S22 S24 emergency stop or LC S32 S34 emergency stop or LC S42 S44 enabling LED en 1 en 2 output 48 LED run 1 error code output 58 erro...

Страница 15: ...elbe Funktion in allen anderen Applikationen Note The times specified in a pulse diagram also apply to the same function in other applications Remarque Les indications de temps d un diagramme sont valables pour la même fonction dans toutes les applications M9190 2 2 2 two hand 1 S32 S34 two hand 2 S42 S44 enabling of the other modules assigned to the same output enabling LED en 1 en 2 output 48 LE...

Страница 16: ... d urgence ou EPES commande bimanuelle IIIC fonctions 6 7 8 ou 9 DE Anwendungsbeispiele EN Application examples FR Exemples d utilisation BG5913 X1 X2 S12 S14 S22 S24 S32 S34 S42 S44 58 48 M9194_b L L LC waiting for start error error indication enabling active emergency stop emergency stop or LC emergency stop or LC trans mitter trans mitter OSSD OSSD BG5913 X1 X2 S12 S14 S22 S24 S32 S34 S42 S44 5...

Страница 17: ... Block Diagram FR Schéma bloc X1 S44 S42 S34 S32 S24 S22 S14 S12 X2 48 58 input module PTC input or control module M8752_a start button assignment output assignment function management en1 en2 run1 run2 S12 S14 S22 S24 S32 S34 S42 S44 48 58 X1 X2 M8741 S12 S24 S32 S34 S42 S44 X1 X2 S14 S22 48 58 A1 A1 ...

Страница 18: ...ns in mm FR Dimensions dimensions en mm DE Montage Demontage der Klemmenblöcke EN Mounting disassembly of the terminal blocks FR Démontage des borniers ammovibles DE Achtung Der Berührungsschutz der angeschlossenen Elemente und die Isolation der Zuleitungen sind für die höchste am SAFEMASTER M System anliegende Spannung auszulegen EN Attention Protection against contact of the connected elements a...

Страница 19: ... ISO 13849 1 Kategorie Category 4 PL e MTTFd 2697 1 a year DCavg 96 0 dop 220 d a days year hop 12 h d hours day tcycle 138 s cycle IEC EN 62061 IEC EN 61508 SIL CL 3 IEC EN 62061 SIL 3 IEC EN 61508 HFT 1 DCavg 96 0 SFF 99 2 PFHD 2 34E 10 h 1 HFT Hardware Fehlertoleranz Hardware failure tolerance Tolérance défauts Hardware Anforderung seitens der Sicherheitsfunktion an das Gerät Intervall für zykl...

Страница 20: ...bung Description Description BH5911 03 00MF0 DC24V Steuereinheit Control Unit Unité centrale BH5911 22 00MF0 DC24V BG5912 04 00000 DC24V Ausgangsmodul Output Module Module de sortie BG5912 48 00000 DC24V BG5912 86 00000 DC24V Tv 0 20S Ausgangsmodul rückfallverzögert Output Module off delay Module de sortie retardés à la chute BG5912 86 00000 DC24V Tv 0 3S BG5912 95 00000 DC24V Tv 0 3S BG5913 08 00...