To select automatic restart terminals S13 - S34 must be bridged, S33 - 
S34 must be opened. Open terminals S13 - S34 select manual restart, the 
On-button must then be connected to S33 - S34.

Line fault detection on On-button:
The line fault detection is only active when the time delayed relais K1

t

 and 

K2

have released and then S12 (channel A) and S32 (channel B) are swit-

ched simultaneously. If the On-button is closed before S12, S32 is connec-
ted to voltage (also when line fault across On-button), the output contacts 
will not close. The unit will not restart before the time delay is finished.

A line fault across the On-button which occurred after activation of the 
relay, will be detected with the next activation and the output contacts will 
not close. If a line fault occurs after the voltage has been connected to 
S12, S32, the unit will be activated because this line fault is similar to the 
normal On-function.
The unit can be operated with single channel and 2-channel operation 
with cross fault monitoring. For connection please refer to application ex-
amples.

The terminal S21 permits the operation of the device in IT-systems with 
insulation monitoring, serves as a reference point for testing the control 
voltage and is used to connect the E-stop loop when cross fault monitoring 
is selected.
Connecting the terminal S21 to the protective ground bridges the internal 
short-circuit protection of Line A2(-). The short-circuit protection of line 
A1(+) remains active.

Input

Nominal voltage U

N

DC 24 V

Voltage range: 

0.9 ... 1.1 U

N

Nominal consumption: 

approx. 3.5 W

Min. Off-time:

 

1 s

Control voltage S11: 

DC 23 V at U

device not activated

Control current via S12, S32:

 

each 40 mA at U

N

Min. voltage
to terminals S12, S32:

 

DC 19 V device not activated

Short-circuit protection:

 

Internal  PTC

Overvoltage protection:

 

Internal  VDR

Output

Contacs: 

2  NO contacts instantaneous, and

  

contact release delay

Operating time typ. at U

N

:

manual start: 

25 ms

automatic start at U

N

100 ms

Release delay typ. at U

N

:

in case of break of
supply voltage: 

20 ms

in case of break of
S12, S22 and S32: 

10 ms

Time delay tv

(release delayed): 

Auxilary supply must be connected for

   

time delay

   

Time ranges:

   

0.1  ...  1 s 

3.0  ...  30 s

   

0.3  ...  3 s 

6.0  ...  60 s

   

0.5  ...  5 s 

30  ...  300 s

   

1.0  ...  10 s

   

Other ranges or values on request

Repeat accuracy:

 

±

 1 % of setting value

Contact type:

 

forcibly guided

Nominal output voltage:

 

AC 250 V

   

DC: see arc limit curve

Max switching current:

 

DC: see arc limit curve

Thermal current I

th

:

 

in 1 contact path: 

13 / 14 or 23 / 24: 

max. 8 A (see quadratic total current limit curve)

37 / 38:  

max. 6 A (see quadratic total current limit curve)

Switching capacity

to AC 15

NO contact: 

3 A / AC 230V 

IEC/EN 60 947-5-1

to DC 13

NO contacts: 

2 A / DC 24 V

Electrical life

to AC 15 at 2 A, AC 230 V: 

10

5

 switching cycles  IEC/EN 60 947-5-1

Permissible operating

frequency:

 

max. 360 switching cycles / h

   

with short release delay time

Short circuit strength

max. fuse rating

13 / 14 or 23 / 24: 

10 A gG / gL 

IEC/EN 60 947-5-1

37 / 38: 

4 A gG / gL 

IEC/EN 60 947-5-1

Line circuit breaker: 

B 6 A 

   

(max. short circuit c 300 A) 

Mechanical life:

 

10 x 10

6

 switching cycles

General Data

Operating mode:

 

Continuous operation

Temperature range

Operation:           

- 25 ... + 55 °C

Storage:        

- 25 ... + 85 °C

Altitude: 

  

< 2.000 m

Clearance and creepage

distances

rated impuls voltage /

pollution degree: 

4 kV / 2 

IEC 60 664-1

EMC 

IEC/EN 61 326-3-1, IEC/EN 62 061

Interference suppression: 

Limit value class B 

EN 55 011

Degree of protection

Housing: 

IP 40 

 

IEC/EN 60 529

Terminals: 

IP 20 

 

IEC/EN 60 529

Housing:

 

Thermoplastic with V0 behaviour

   

according to UL subject 94

Vibration resistance:

 

Amplitude 0.35 mm,

  

frequency 10 ... 55 Hz  IEC/EN 60 068-2-6

Climate resistance:

 

25 / 055 / 04 

IEC/EN 60 068-1

Terminal designation:

 

EN 50 005

Wire fixing:

 

Plus-minus terminal screws M3.5 box 

   

terminals with wire protection

Mounting:

 

DIN rail 

IEC/EN 60 715

Weight:

 

approx. 210 g

Dimensions

Width x height x depth:

 

LG 5928: 

22.5 x   90 x 121 mm

LG 5928PC: 

22.5 x 111 x 121 mm

LG 5928PS: 

22.5 x 104 x 121 mm

Terminal designation

Signal description

A1(+)

+ / L

A2 (-)

- / N

S11, S21, S13, S33

Inputs

S12, S22, S32, S34

Outputs

13, 14, 23, 24

Positive driven NO contacts for 
release circuit

37, 38

Positive guided No contacts for 
release delay circuit

Technical Data

Technical Data

Notes

Connection Terminals

Содержание SAFEMASTER LG 5928

Страница 1: ...Not Aus Modul mit Zeitverz gerung LG 5928 0264221 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays do...

Страница 2: ...5 Schaltbilder 6 Anschlussklemmen 6 Hinweise 6 Technische Daten 6 Technische Daten 7 UL Daten 7 Standardtype 7 Bestellbeispiel 7 Vorgehen bei St rungen 8 Wartung und Instandsetzung 8 Kennlinie 8 Kennl...

Страница 3: ...n im Notfall kein automatischer Start erfolgen Deshalb muss in den Betriebs arten mit automatischem Start eine bergeordnete Steuerung einen automatischen Start nach einem Not Aus verhindern Durch ffne...

Страница 4: ...4 LG 5928 13 12 18 de 047A...

Страница 5: ...aren Anschlussbl cken f r schnellen Ger teaustausch optional mit Schraubklemmen oder mit Federkraftklemmen 22 5 mm Baubreite 0257328 Schutz von Personen und Maschinen Not Aus Schaltungen von Maschinen...

Страница 6: ...bei UN 100 ms R ckfallzeit typ bei UN bei Unterbrechung der Versorgungsspannung 20 ms bei Unterbrechung in S12 S22 und S32 10 ms Zeitverz gerung tv r ckfallverz gert F r den Zeitablauf ist die Spannu...

Страница 7: ...83 Ausgang 2 Schlie er sofort und 1 Schlie er r ckfallverz gert Nennspannung UN DC 24 V Zeitverz gerung tv 1 10 s Baubreite 22 5 mm UL Daten Standardtype LG 5928 41 61 mit einstellbarer Zeitverz gerun...

Страница 8: ...t gestartet werden Die verz gerten Kontakte sind noch nicht abgefallen Ein Sicherheitsrelais ist verschwei t Ger t austauschen Mindestens eine der Verbindungen S11 S12 S11 S32 S21 S22 fehlt Handstart...

Страница 9: ...durch Einschleifen der ffnerkontakte in den Einschaltkreis S13 S34 oder S33 S34 berwacht Geeignet bis SIL3 Performance Level e Kat 4 S11 S32 M9843_a L1 N Not Aus A2 A1 S11 S33 S34 S12 S22 S21 LG5928 4...

Страница 10: ...10 LG 5928 13 12 18 de 047A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Postfach 1251 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Страница 11: ...top Module with time delay LG 5928 Datasheet Operating Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold co...

Страница 12: ...nnection Terminals 16 Notes 16 Technical Data 16 Technical Data 17 UL Data 17 Standard Type 17 Ordering Example 17 Troubleshooting 18 Maintenance and repairs 18 Characteristics 18 Characteristics 18 A...

Страница 13: ...line fault is similar to the normal On function AUTOMATIC START According to IEC EN 60 204 1 part 9 2 5 4 2 and 10 8 3 it is not allowed to restart automatically after emergency stop Therefore the mac...

Страница 14: ...14 LG 5928 13 12 18 en 047A...

Страница 15: ...28 1 2 3 As option with pluggable terminal blocks for easy exchange of devices with screw terminals or with cage clamp terminals Width 22 5 mm 0258918 Protection of people and machines Emergency stop...

Страница 16: ...case of break of supply voltage 20 ms in case of break of S12 S22 and S32 10 ms Time delay tv release delayed Auxilary supply must be connected for time delay Time ranges 0 1 1 s 3 0 30 s 0 3 3 s 6 0...

Страница 17: ...G 20 16 Str Torque 0 8 Nm Plug in cage clamp AWG 20 12 Sol Str nfo Technical data that is not stated in the UL Data can be found in the technical data section UL Data Standard Type LG 5928 41 61 with...

Страница 18: ...not yet switched off Safety relay is welded replace device Min one of this connection is not present S11 S12 S11 S32 S21 S22 Manual start mode Line fault on start button disconnect power supply and r...

Страница 19: ...by one contact path S33 S34 must stay open on auto start Suited up to SIL3 Performance Level e Cat 4 if the external contactors are in the same cabinet and the wiring is short circuit and crossfault...

Страница 20: ...20 LG 5928 13 12 18 en 047A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 77 23 654 356...

Страница 21: ...r t d urgence avec temporisation LG 5928 Fiche Technique Manuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www...

Страница 22: ...t ristiques techniques 26 Caract ristiques techniques 27 Donn es UL 27 Versions standard 27 Exemple de commande 27 Diagnostics des d fauts 28 Entretien et remise en tat 28 Courbe caract ristiques 28 C...

Страница 23: ...d marrage automatique apr s un Arr t d urgence Losqu un d marrage automatique est toutefois demand il est nec ssaire de assurer qu une commande prioritaire effectue le blocage apr s une action d arr t...

Страница 24: ...24 LG 5928 13 12 18 fr 047A...

Страница 25: ...ec 2 cercles de temps ind pendamment r glables pour la tension assign e AC DC 24 V shunt sur S13 S14 Largeur utile 22 5 mm 0260725 Protection des personnes et machines Couplages d arr t d urgence des...

Страница 26: ...dans S12 S22 et S32 10 ms Temporisation tv retard e la chute La tension d alimentation est n cessaire pour le d roulement de la temporisation Plages de temps 0 1 1 s 3 0 30 s 0 3 3 s 6 0 60 s 0 5 5 s...

Страница 27: ...orque 0 8 Nm bornes PC AWG 20 12 Sol Str nfo Les valeurs techniques qui ne sont pas sp cifi es ci dessus sont sp cifi es dans les valeurs techniques g n rales Donn es UL Version standard LG 5928 41 61...

Страница 28: ...ontacts du relais sont soud s remplacer l appareil Il manque minimum une liaison entre S11 S12 S11 S32 S21 S22 Mode de r enclenchement manuel Erreur de ligne sur le bouton Marche d brancher l alimenta...

Страница 29: ...ouplage d arr t d urgence un canal Ce couplage n a pas de redon dance dans le circuit des metteurs d ordres d arr t d urgence Convient jusqu SIL3 Performance Level e Cat 3 Amplification des contacts s...

Страница 30: ...30 LG 5928 13 12 18 fr 047A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com B P 1251 T l phone 49 77 23 654 0 T l fax 49 77 23 654 356...

Страница 31: ...m2 2 x AWG 20 to 16 A 10 12 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 A 12 mm 1 x 0 5 4 mm2 1 x AWG 20 to 12 M10249 A A 8 mm 1 x 0 5 2 5 mm2 1 x AWG 20 to 14 2 x 0 5 1 5 mm2 2 x AWG 20 to 16 A 8 mm 1 x 0 5...

Страница 32: ...endreher um seine L ngsachse drehen 4 Beachten Sie bitte dass die Klemmenbl cke nur auf dem zugeh rigen Steckplatz montiert werden EN Removing the terminal blocks with cage clamp terminals 1 The unit...

Страница 33: ...10 h 1 T1 20 a year HFT Hardware Fehlertoleranz Hardware failure tolerance Tol rance d fauts Hardware DE Sicherheitstechnische Kenndaten nur verz gerte Kontakte EN Safety related data only delayed con...

Страница 34: ...34 LG 5928 13 12 18 de en fr 047A DE EG Konformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne...

Страница 35: ...35 LG 5928 13 12 18 de en fr 047A DE Notizen EN Notice FR Note...

Страница 36: ...36 LG 5928 13 12 18 de en fr 047A E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Отзывы: