16
LG 5928 / 13.12.18 en / 047A
To select automatic restart terminals S13 - S34 must be bridged, S33 -
S34 must be opened. Open terminals S13 - S34 select manual restart, the
On-button must then be connected to S33 - S34.
Line fault detection on On-button:
The line fault detection is only active when the time delayed relais K1
t
and
K2
t
have released and then S12 (channel A) and S32 (channel B) are swit-
ched simultaneously. If the On-button is closed before S12, S32 is connec-
ted to voltage (also when line fault across On-button), the output contacts
will not close. The unit will not restart before the time delay is finished.
A line fault across the On-button which occurred after activation of the
relay, will be detected with the next activation and the output contacts will
not close. If a line fault occurs after the voltage has been connected to
S12, S32, the unit will be activated because this line fault is similar to the
normal On-function.
The unit can be operated with single channel and 2-channel operation
with cross fault monitoring. For connection please refer to application ex-
amples.
The terminal S21 permits the operation of the device in IT-systems with
insulation monitoring, serves as a reference point for testing the control
voltage and is used to connect the E-stop loop when cross fault monitoring
is selected.
Connecting the terminal S21 to the protective ground bridges the internal
short-circuit protection of Line A2(-). The short-circuit protection of line
A1(+) remains active.
Input
Nominal voltage U
N
:
DC 24 V
Voltage range:
0.9 ... 1.1 U
N
Nominal consumption:
approx. 3.5 W
Min. Off-time:
1 s
Control voltage S11:
DC 23 V at U
N
device not activated
Control current via S12, S32:
each 40 mA at U
N
Min. voltage
to terminals S12, S32:
DC 19 V device not activated
Short-circuit protection:
Internal PTC
Overvoltage protection:
Internal VDR
Output
Contacs:
2 NO contacts instantaneous, and
1
contact release delay
Operating time typ. at U
N
:
manual start:
25 ms
automatic start at U
N
:
100 ms
Release delay typ. at U
N
:
in case of break of
supply voltage:
20 ms
in case of break of
S12, S22 and S32:
10 ms
Time delay tv
(release delayed):
Auxilary supply must be connected for
time delay
Time ranges:
0.1 ... 1 s
3.0 ... 30 s
0.3 ... 3 s
6.0 ... 60 s
0.5 ... 5 s
30 ... 300 s
1.0 ... 10 s
Other ranges or values on request
Repeat accuracy:
±
1 % of setting value
Contact type:
forcibly guided
Nominal output voltage:
AC 250 V
DC: see arc limit curve
Max switching current:
DC: see arc limit curve
Thermal current I
th
:
in 1 contact path:
13 / 14 or 23 / 24:
max. 8 A (see quadratic total current limit curve)
37 / 38:
max. 6 A (see quadratic total current limit curve)
Switching capacity
to AC 15
NO contact:
3 A / AC 230V
IEC/EN 60 947-5-1
to DC 13
NO contacts:
2 A / DC 24 V
Electrical life
to AC 15 at 2 A, AC 230 V:
10
5
switching cycles IEC/EN 60 947-5-1
Permissible operating
frequency:
max. 360 switching cycles / h
with short release delay time
Short circuit strength
max. fuse rating
13 / 14 or 23 / 24:
10 A gG / gL
IEC/EN 60 947-5-1
37 / 38:
4 A gG / gL
IEC/EN 60 947-5-1
Line circuit breaker:
B 6 A
(max. short circuit c 300 A)
Mechanical life:
10 x 10
6
switching cycles
General Data
Operating mode:
Continuous operation
Temperature range
Operation:
- 25 ... + 55 °C
Storage:
- 25 ... + 85 °C
Altitude:
< 2.000 m
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
4 kV / 2
IEC 60 664-1
EMC
IEC/EN 61 326-3-1, IEC/EN 62 061
Interference suppression:
Limit value class B
EN 55 011
Degree of protection
Housing:
IP 40
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Housing:
Thermoplastic with V0 behaviour
according to UL subject 94
Vibration resistance:
Amplitude 0.35 mm,
frequency 10 ... 55 Hz IEC/EN 60 068-2-6
Climate resistance:
25 / 055 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire fixing:
Plus-minus terminal screws M3.5 box
terminals with wire protection
Mounting:
DIN rail
IEC/EN 60 715
Weight:
approx. 210 g
Dimensions
Width x height x depth:
LG 5928:
22.5 x 90 x 121 mm
LG 5928PC:
22.5 x 111 x 121 mm
LG 5928PS:
22.5 x 104 x 121 mm
Terminal designation
Signal description
A1(+)
+ / L
A2 (-)
- / N
S11, S21, S13, S33
Inputs
S12, S22, S32, S34
Outputs
13, 14, 23, 24
Positive driven NO contacts for
release circuit
37, 38
Positive guided No contacts for
release delay circuit
Technical Data
Technical Data