Maintenance of the multifunction safety module BI 5910 with radio control
Please check the following points:
• The wiring of BI 5910 with the circuits of the controlled machine
• The correct function of active and passive disconnection
• Seal of aerial
• Connection of aerial and cleanness and oxidation of aerial
To check active disconnection
press e-stop button. The safety relays of the receiver must
de-energise immediately.
To check passive disconnection
remove the electronic key from the remote control the
safety relays of the receiver must disconnect within less the 0.5 seconds.
Pare parts:
The only necessary spare part is the battery of the remote control RE 5910
RE 5910/050:
Battery for RE 5910
see appendix E (change of the battery)
11
Maintenance
Maintenance of the multifunction safety module BI 5910 with radio control
Please check the following points:
• The wiring of BI 5910 with the circuits of the controlled machine
• The correct function of active and passive disconnection
• Seal of aerial
• Connection of aerial and cleanness and oxidation of aerial
To check active disconnection
press e-stop button. The safety relays of the receiver must
de-energise immediately.
To check passive disconnection
remove the electronic key from the remote control the
safety relays of the receiver must disconnect within less the 0.5 seconds.
Pare parts:
The only necessary spare part is the battery of the remote control RE 5910
RE 5910/050:
Battery for RE 5910
see appendix E (change of the battery)
11
Maintenance