105
105
5.
Technical data
5.2
Multifunction safety module BI 5910
Fusing:
Internal with PTC
Max. time difference
between input signals
of one function
E-stop, Light curtains:
250 ms
Gates:
3 s
Safety Output
Contacts
BI 5910.03:
3 NO contacts
BI 5910.22:
2 NO contacts, 1 NC contact
The NC contact can only be used as indicator contact!
Contact type:
Relay, positive guided
Pic up time typ. at U
N
automatic start:
max. 800 ms
manual start:
max. 110 ms
automatic restart:
max. 70 ms
5.
Technical data
5.2
Multifunction safety module BI 5910
Fusing:
Internal with PTC
Max. time difference
between input signals
of one function
E-stop, Light curtains:
250 ms
Gates:
3 s
Safety Output
Contacts
BI 5910.03:
3 NO contacts
BI 5910.22:
2 NO contacts, 1 NC contact
The NC contact can only be used as indicator contact!
Contact type:
Relay, positive guided
Pic up time typ. at U
N
automatic start:
max. 800 ms
manual start:
max. 110 ms
automatic restart:
max. 70 ms