SPECIFIC CONDITIONS OF USE 

 

SPECIFIC CONDITIONS OF USE 

 

 

SPECIFIC CONDITIONS OF USE 

INSTALLATION / SET-UP 

The units must be installed, connected and set up by qualified staff. The qualified staff must have knowledge of protection classes, 
regulations and provisions for apparatus in hazardous areas. 
Check whether the classification (see "Marking" above and marking on the unit) is suitable for the application. 

 
INSTALLATION REMARKS / INSTALLATION 

 

Make sure only qualified personnel performs the installation/maintenance/service. 
Before removing the sensor, or before connecting or disconnecting the wiring, turn off the power supply. Do not 
disconnect, unless the area is non-explosive. 
Verify that the environmental temperature is within the temperature class required for the area. 

 

 

Ambient temperature range is -30 °C to +50 °C. 

 

Never remove the trimmer cover protector unless the area is non-explosive. 

 

Adhere to the relevant national regulations and provisions. 

 

The relevant installation regulations must be adhered to. In particular, take into account the requirements relating 
to the temperature limitation as regards the expected dust deposits. 

 

Avoid electrostatic charging on housings and cables 

 

In case of cleaning the sensor, this must be done with a damp cloth, in order to prevent build-up of electrostatic 
charges. 

 

If fast moving particles are present a physical barrier shall protect the sensor. 

 

Cable shall be protected from pulling or twisting. 

 

The sensor may only be connected/supplied from a circuit having a prospective short circuit current of not 
greater than 10kA. 

 

The sensor must be protected against exposure to direct sunlight and other ultraviolet light sources. 

 

The sensor is manufactured with a permanently mounted cable gland and permanently connected cable that is 
non-replaceable and shall be terminated in a safe area or in a suitable certified termination box. 

 

If the user reduces the sensitivity to almost minimum, the sensor will not be able to detect objects in front of it. In 
this fail situation, the internal relay will always be ON but the temperature class 85

 o

C will never be exceeded. 

 

 

Содержание 46R

Страница 1: ...C T200 85 o C Da The DOL 46R capacitive relay sensor series is designed for general detection of feed grain and solids Certified according to ATEX directive 2014 34 EU and IECEx for operation in potential explosive dust atmospheres Classified as equipment for use in atmospheres with continuous presence of explosive dust with an ignition temperature above 85 oC Robust design with plastic housing wi...

Страница 2: ... Use the black wires 1 and 4 NOTE The internal relay is in position NC when the supply voltage is connected and the sensor is activated wire 1 and 4 are connected Figure 2 No current sensor USER S GUIDE Easy trimmer adjustment on a single turn 240 trimmer with linear or non linear scale Functions which can be made available for adjustment on trimmers ON and or OFF delay MaxRunTimer Sensitivity DOL...

Страница 3: ... non explosive Adhere to the relevant national regulations and provisions The relevant installation regulations must be adhered to In particular take into account the requirements relating to the temperature limitation as regards the expected dust deposits Avoid electrostatic charging on housings and cables In case of cleaning the sensor this must be done with a damp cloth in order to prevent buil...

Страница 4: ... all remaining risk areas but mines 1 Category 1 The sensor can be used in zone 20 Flammable material present continuously or long periods 21 Flammable material present occasionally 22 Flammable material present in abnormal conditions for short periods D For use in hazardous areas in which explosive dust are present Ex Conforms to the Harmonized Standards ta Protection by enclosure highest level I...

Отзывы: