2.3.3. Connecting signaling devices  

 

 
Signaling or other devices can be connected to each monitored output 

OUT 1, OUT2 

- Fig. 10. 

Device’s 

maximum  consumption  shall  not  exceed  0.5A. 

A  4.7  кОhm  terminating  resistor 

must

  be  connected  in 

parallel to the loop. 

 

+

O

U

T

1

-

R
4.7k

 

 

 

Fig. 10 

– Example of an exit sign device connected to an output  

 

  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

  

 

Monitored outputs OUT1 and OUT2 provide 24VDC 0.5A to load, connected between 

them and a mass*.  

  A 

4.7 кОhm terminating resistor shall be connected in parallel to the device far off 

from the panel in the loop, so the panel is able to check the loop integrity 

– see Fig.10. 

 

Содержание FP9000A

Страница 1: ...DMTech LTD Pleven Addressable Fire Alarm Panel FP9000A Instruction manual for installation setup and exploitation Revision 01 19 ...

Страница 2: ...e the final installation of the panel and the fire detectors The design includes assigning an address to each device and planning a name for it maximum length 20 symbols spaces included so it can be easily found in the configured system The devices shall be grouped in zones in compliance with current standards applicable to installation of fire alarm systems and according to building blueprints 1 ...

Страница 3: ...vents with registered date and time of occurring Programming option for Day Night Mode of Operation Operation menus in Bulgarian English language Setup via computer and USB using software Developed in compliance with the requirements of EN54 2 4 Standard Wall mounted box case 313х218х85 and lid 314х219x18 1 2 2 Operational environment Protection degree IP30 Ambient temperature 5ºС to 40ºC Relative...

Страница 4: ...city of outputs OUT1 and OUT2 500 mA DC Maximum load capacity of outputs FIRE FAULT and EXT 300 mA DC Maximum total load sum up of the 4 above 2 0 A DC Programmable relay outputs 1A 24VDC List of fuses Main power supply 4А T type slow melting 5х20 mm Storage battery 6 0А T type slow melting 5х20 mm Contents of delivery Addressable Fire Alarm System FP9000A 1 Fire alarm panel FP 9000А 1 pc 2 Fuse 6...

Страница 5: ... SABLE 2 3 4 5 6 7 8 PO W ER SYSER R TR AN SM C O M M U N O U TSD ELAYO U T O N 1500mm 300mm ESC FIRE 1 DISTFIRE F AUL T TEST DISABL E 2 3 4 5 6 7 8 POW ER SYS ERR TRANSMCOMMUN OUTS DEL A Y OUT ON N L Fuse 4A FP9000A 1 3 2 Fig 1 Fig 2 In compliance with the dimensions provided in Fig 3 drill holes in the mounting surface Drill holes in the wall and fasten the box All external cables must be pulled...

Страница 6: ...l mounting holes 2 Holes for pulling cables through 3 Holes for pulling main supply cable through 4 Additional holes for cable pulling 2 2 170 mm 240 mm 1 3 5 a b c 313 mm 218 mm 85 mm Fuse 4A N L Fuse 4A to panel Fuse 4A 220V 10 50 60 Hz No EN54 2 1997 A1 2006 AC 2009 EN54 4 1997 A2 2006 AC 2009 IP30 TYPE FP9000A Pb U 187 2 V 50 60Hz P 45VA 44 N E Str Pleven 1 А7 5800 xarch Joseph Bulgaria www dm...

Страница 7: ...d to panel s output DIST FIRE DISTANT FIRE INDICATOR Illuminates continuously in red in case of alarm for fire event in a distant fire alarm panel after received signal from automated fire detector manual call point or from another external device connected to distant panel s outputs FAULT FAULT Illuminates continuously in yellow in case of fault event in the system TEST TEST Illuminates continuou...

Страница 8: ...s an interrupted signal 3 Description of LCD display The fire alarm panel has an alphanumeric LCD display 4 lines x 20 symbols It displays information on registered events The display visualizes menus for panel settings menus are tree structured see Fig 11 that can be accessed consecutively using the navigation buttons The user can assign freely names to zones and devices using the buttons for nav...

Страница 9: ...creases a highlighted value with one step or enables access to a descending menu EXIT button ESC Exiting the menu The button is for exiting the menu It is active at access level 1 2 and 3 2 2 2 Position of modules in the box Fig 5 Position of modules in the box 1 Box leveling ampule 2 220V terminal for main power supply cable 3 Main PCB with built in power supply 4 Chassis with ready to use alphan...

Страница 10: ... the panel is in fault mode 3 positions provided for Nc default condition and No condition OUT1 Monitored output OUT1 a 4 7 кОhm terminating resistor shall be connected in parallel to the device far off from the panel OUT2 Monitored output OUT2 a 4 7 кОhm terminating resistor shall be connected in parallel to the device far off from the panel RELAY 1 Programmable relay 1 the relay function shall b...

Страница 11: ...nd the power supply unit is done by the producer The connection between the main power supply cable and the 220V terminal is shown in Fig 3 2 2 5 Connecting the storage battery Storage battery connecting pins are situated at the base of the PCB The connection to the storage battery is shown in Fig 7 The fire alarm panel box has a cable with installed cable ear terminals for serial connection of st...

Страница 12: ...last device and each 25th device in the loop have a built in short circuit isolator The cross section and the Ohm resistance of the cable used for connecting the devices to the loop shall be carefully assessed the loop length varies For convenience a calculator has been developed for calculating the loop length and the cable cross section according to specified number and type of devices LOOP 1 1 ...

Страница 13: ...T 1 OUT2 Fig 10 Device s maximum consumption shall not exceed 0 5A A 4 7 кОhm terminating resistor must be connected in parallel to the loop OUT1 R 4 7k Fig 10 Example of an exit sign device connected to an output Monitored outputs OUT1 and OUT2 provide 24VDC 0 5A to load connected between them and a mass A 4 7 кОhm terminating resistor shall be connected in parallel to the device far off from the...

Страница 14: ... password is required 3 Setup 1 Panel Param 2 LAN Param 3 Param Loop 4 Param Devices 5 Conv Line Param 6 Zones 1 1 L o o p O N 2 6 D e vice s 3 C u rr sh o rt 5 0 0 Lang English Earth Check ON LAN Address 0000 Panel Master 1 Cоnv Line ON OFF 2 Zone oved ON OFF 3 Rem Det 4 N Check 2 o 5 Interr 2 А Current m 6 Fire 10 А Current m 7 Short 80 А Current m 8 Z Param one 1 Zone 1 n Zone n 1 Zone Param 2 ...

Страница 15: ...nel operates in two modes DAY MODE and NIGHT MODE 3 2 5 Test indication activates a test mode allowing to perform functionality check of panel s light indication checking the functionality of the light indication of the panel 3 3 SETUP Menu to access the menu a password for access level 3 is required 3 3 1 Panel parameters the menu provides access to options for changing panel s language settings ...

Страница 16: ... functionality check on panel outputs and addressable devices outputs М9000А IO Panel outputs check is performed by manual activation of each output marked with a tick in the menu Addressable outputs check is performed by selecting the address of the device that will be tested analogically as in menu Check Address 3 3 9 Passwords allows setting a password for access level 2 and 3 Access level 2 se...

Страница 17: ...number from the available numbers at his choice 5 Assigning names to devices and adding devices to a LOOP To ensure easy orientation the fire alarm panel allows assigning an individual name to each device The devices also can be grouped in ZONES 5 1 Assigning names to devices Enter Settings menu Device Parameters Fig 11 pos 3 4 Use the arrows to see the parameters of the device To enter a text sel...

Страница 18: ... are added in this menu EXAMPLE Let s assume that devices are allocated in a building as follows 1 Automated fire detectors 10 devices on each floor A1R A1S SR MSR 2 Manual call points MCP 3 on each floor 3 Sound and light indicator S9000A 2 on each floor We assume that each device has been addressed and has an individual address point 4 Each device has a name p 5 For example the manual call point...

Страница 19: ...ON 5 2 1 Mounting 5 2 2 System elements 7 2 2 1 Front panel 7 2 2 2 Position of modules in the box 9 2 2 3 Description of main PCB 10 2 2 4 Connecting the main supply 11 2 2 5 Connecting the storge battery 11 2 3 Connecting devices 12 2 3 1 Connecting devices to a loop 12 2 3 2 Connecting devices to a conventional line 12 2 3 3 Connecting signaling devices 13 3 Program menus and settings of the fi...

Страница 20: ...Instruction manual Fire Alarm Panel FP9000A DMTech LTD 16 N Haytov Street Pleven Tel 0889992660 e mail office dmtech ltd com page 20 of 20 ISO 9001 2015 Certified Company ...

Отзывы: