Instruction manual
Fire Alarm Panel FP9000A
DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:[email protected] page - 13 - of 20
ISO 9001:2015 Certified Company
2.3.3. Connecting signaling devices
Signaling or other devices can be connected to each monitored output
OUT 1, OUT2
- Fig. 10.
Device’s
maximum consumption shall not exceed 0.5A.
A 4.7 кОhm terminating resistor
must
be connected in
parallel to the loop.
+
O
U
T
1
-
R
4.7k
Fig. 10
– Example of an exit sign device connected to an output
Monitored outputs OUT1 and OUT2 provide 24VDC 0.5A to load, connected between
them and a mass*.
A
4.7 кОhm terminating resistor shall be connected in parallel to the device far off
from the panel in the loop, so the panel is able to check the loop integrity
– see Fig.10.