Instruction manual
Fire Alarm Panel FP9000A
DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:[email protected] page - 4 - of 20
ISO 9001:2015 Certified Company
•
Voltage: 90
~
264 VAC
•
Frequency: 50/60 Hz
Backup battery supply
•
Charge voltage (U): 27.3V
•
Storage battery: 2 x 12V / 5Ah, lead-acid, encapsulated
•
Storage battery internal resistance
Ri: < 0.3Ω
•
Storage battery maximum dimensions: 2 pcs
– 90х98х70mm
•
Type of connection to battery: cable terminal
Load capacity
•
Maximum load capacity of loop: 500 mA DC
•
Maximum load capacity of
AUX
: 500 mA DC
•
Maximum load capacity of outputs
OUT1
and
OUT2
: 500 mA DC
•
Maximum load capacity of outputs
FIRE
,
FAULT
and
EXT
: 300 mA DC
•
Maximum total load (sum up of the 4 above): 2.0 A DC
•
Programmable relay outputs: 1A@24VDC
List of fuses
•
Main power supply
: 4А, T-type, slow-melting, 5х20 mm
•
Storage battery: 6
.0А, T-type, slow-melting, 5х20 mm
•
Contents of delivery: Addressable Fire Alarm System FP9000A
1
Fire alarm panel FP
9000А
1 pc
2
Fuse 6,3
А
1 pc
3
Fuse
4,0А
1 pc
4
Jumper for backup batteries
1 pc
5
Packing
1 pc
6
Resistor
4.7кΩ
3 pcs
WARNING!
The fire alarm panel must be installed by a qualified staff only.
Panel’s electronic components are vulnerable to electrostatic discharge.
DO NOT make any hardware changes in panel’s configuration while the panel is powered
by grid or backup batteries.