Manual addressing 

(Fig.11 position 3.7.2.) 

– as soon as a device is 

attached to its base, the fire alarm panel recognizes it and suggests 
a sequential address, but awaits confirmation. A specific number can 
be assigned to each device in this menu (once an address has been 
selected, it’s not suggested again)   

 

4.3. Where

  Auto  addressing 

  is  selected,  the  message  ADD 

DEVICE  is  displayed  (Fig.11  pos.  3.7.1.).  As  soon  as  the 
addressable  device  is  physically  attached  to  the  base,  its  light 
indicators  start  illuminating  and  the  message  ADDRESS  FOR 
ADDRESSING appears on the display. The address is accepted 
automatically then the message PLEASE WAIT appears on the 
display. As soon as the device is recognized and its address is 
programed, the message  ADD DEVICE is displayed again and 
the panel waits for a next device to be added. This sequence is 
repeated until all devices are added to the loop. 

 
4.4. Where

 Manual addressing 

 is selected (Fig.11 position 3.7.2.),

 

the sequence of actions is the same as in auto addressing; the 
only difference is that the fire alarm panel suggests an address 
and  waits  until  it  is  selected  and  confirmed. The  user  then  has 
the option to use sequential numbers as addresses or to assign 
a specific number (from the available numbers) at his choice.  
 
 

5.   Assigning names to devices and adding 

devices to a LOOP

.

 

 

To ensure easy orientation, the fire alarm panel allows assigning an 

individual name to each device. The devices also can be grouped in 
ZONES. 

 

5.1.  Assigning  names  to  devices.  Enter  Settings  menu  ->  Device 

Parameters  (Fig.11  pos.  3.4.).  Use  the  arrows  to  see  the 
parameters  of  the  device.  To  enter  a  text  select  the  letters 
consecutively.   

 
5.2.  Assigning  names  to  zones  and  adding  devices  to  zones.  Enter 

Settings menu and select ZONES submenu (Fig.11 pos. 3-6.) As 
each zone is set, the menu automatically includes it.   

 
5.2.1. 

Zone Parameters

. The following zone parameters can be set 

in this menu: 

-  Priority Manual Call Point: Prioritized activation through a manual 

call point ON/OFF. Where the set priority is ON and the manual 
call point is activated, the fore alarm panel enters FIRE ALARM 
mode regardless of any other settings for this zone. 

-  Coincidence  Mode:  The  options  are  ON/OFF.  After  one  fire 

detector is activated, the fire alarm panel waits for a signal from 
a second detector before entering FIRE ALARM mode.  
  

-  Delayed Outputs: After a delay is set, the zone will be activated 

A:001 Zn:99 Type: A1S 
  ON      V 02 
SUGGESTED NAME  

 

ADRRESS FOR ADDRESSING 

10 

PLEASE WAIT 

 

ADD DEVICE 

>Call Point Priority:   OFF 
  Coincidence Mode:  OFF 
  Delayed Outputs:        20  
  ZONE1 

>  1 Auto Addressing 
    2 Manual Addressing 
    3 Read Device Param 
    4 Check Address 
 

    2 LAN Param 
    3 Loop Param  
 > 4 Device Param  
    5 Conv Line Param  

    4 Device Param  
    5 Conv Line Param 
 > 6 Zones 
    7 Initialization 
 

 > 1 Zone Param  
    2 Devices 
    3 Outputs w/t Delay 
    4 Delayed Outputs 
 

Содержание FP9000A

Страница 1: ...DMTech LTD Pleven Addressable Fire Alarm Panel FP9000A Instruction manual for installation setup and exploitation Revision 01 19 ...

Страница 2: ...e the final installation of the panel and the fire detectors The design includes assigning an address to each device and planning a name for it maximum length 20 symbols spaces included so it can be easily found in the configured system The devices shall be grouped in zones in compliance with current standards applicable to installation of fire alarm systems and according to building blueprints 1 ...

Страница 3: ...vents with registered date and time of occurring Programming option for Day Night Mode of Operation Operation menus in Bulgarian English language Setup via computer and USB using software Developed in compliance with the requirements of EN54 2 4 Standard Wall mounted box case 313х218х85 and lid 314х219x18 1 2 2 Operational environment Protection degree IP30 Ambient temperature 5ºС to 40ºC Relative...

Страница 4: ...city of outputs OUT1 and OUT2 500 mA DC Maximum load capacity of outputs FIRE FAULT and EXT 300 mA DC Maximum total load sum up of the 4 above 2 0 A DC Programmable relay outputs 1A 24VDC List of fuses Main power supply 4А T type slow melting 5х20 mm Storage battery 6 0А T type slow melting 5х20 mm Contents of delivery Addressable Fire Alarm System FP9000A 1 Fire alarm panel FP 9000А 1 pc 2 Fuse 6...

Страница 5: ... SABLE 2 3 4 5 6 7 8 PO W ER SYSER R TR AN SM C O M M U N O U TSD ELAYO U T O N 1500mm 300mm ESC FIRE 1 DISTFIRE F AUL T TEST DISABL E 2 3 4 5 6 7 8 POW ER SYS ERR TRANSMCOMMUN OUTS DEL A Y OUT ON N L Fuse 4A FP9000A 1 3 2 Fig 1 Fig 2 In compliance with the dimensions provided in Fig 3 drill holes in the mounting surface Drill holes in the wall and fasten the box All external cables must be pulled...

Страница 6: ...l mounting holes 2 Holes for pulling cables through 3 Holes for pulling main supply cable through 4 Additional holes for cable pulling 2 2 170 mm 240 mm 1 3 5 a b c 313 mm 218 mm 85 mm Fuse 4A N L Fuse 4A to panel Fuse 4A 220V 10 50 60 Hz No EN54 2 1997 A1 2006 AC 2009 EN54 4 1997 A2 2006 AC 2009 IP30 TYPE FP9000A Pb U 187 2 V 50 60Hz P 45VA 44 N E Str Pleven 1 А7 5800 xarch Joseph Bulgaria www dm...

Страница 7: ...d to panel s output DIST FIRE DISTANT FIRE INDICATOR Illuminates continuously in red in case of alarm for fire event in a distant fire alarm panel after received signal from automated fire detector manual call point or from another external device connected to distant panel s outputs FAULT FAULT Illuminates continuously in yellow in case of fault event in the system TEST TEST Illuminates continuou...

Страница 8: ...s an interrupted signal 3 Description of LCD display The fire alarm panel has an alphanumeric LCD display 4 lines x 20 symbols It displays information on registered events The display visualizes menus for panel settings menus are tree structured see Fig 11 that can be accessed consecutively using the navigation buttons The user can assign freely names to zones and devices using the buttons for nav...

Страница 9: ...creases a highlighted value with one step or enables access to a descending menu EXIT button ESC Exiting the menu The button is for exiting the menu It is active at access level 1 2 and 3 2 2 2 Position of modules in the box Fig 5 Position of modules in the box 1 Box leveling ampule 2 220V terminal for main power supply cable 3 Main PCB with built in power supply 4 Chassis with ready to use alphan...

Страница 10: ... the panel is in fault mode 3 positions provided for Nc default condition and No condition OUT1 Monitored output OUT1 a 4 7 кОhm terminating resistor shall be connected in parallel to the device far off from the panel OUT2 Monitored output OUT2 a 4 7 кОhm terminating resistor shall be connected in parallel to the device far off from the panel RELAY 1 Programmable relay 1 the relay function shall b...

Страница 11: ...nd the power supply unit is done by the producer The connection between the main power supply cable and the 220V terminal is shown in Fig 3 2 2 5 Connecting the storage battery Storage battery connecting pins are situated at the base of the PCB The connection to the storage battery is shown in Fig 7 The fire alarm panel box has a cable with installed cable ear terminals for serial connection of st...

Страница 12: ...last device and each 25th device in the loop have a built in short circuit isolator The cross section and the Ohm resistance of the cable used for connecting the devices to the loop shall be carefully assessed the loop length varies For convenience a calculator has been developed for calculating the loop length and the cable cross section according to specified number and type of devices LOOP 1 1 ...

Страница 13: ...T 1 OUT2 Fig 10 Device s maximum consumption shall not exceed 0 5A A 4 7 кОhm terminating resistor must be connected in parallel to the loop OUT1 R 4 7k Fig 10 Example of an exit sign device connected to an output Monitored outputs OUT1 and OUT2 provide 24VDC 0 5A to load connected between them and a mass A 4 7 кОhm terminating resistor shall be connected in parallel to the device far off from the...

Страница 14: ... password is required 3 Setup 1 Panel Param 2 LAN Param 3 Param Loop 4 Param Devices 5 Conv Line Param 6 Zones 1 1 L o o p O N 2 6 D e vice s 3 C u rr sh o rt 5 0 0 Lang English Earth Check ON LAN Address 0000 Panel Master 1 Cоnv Line ON OFF 2 Zone oved ON OFF 3 Rem Det 4 N Check 2 o 5 Interr 2 А Current m 6 Fire 10 А Current m 7 Short 80 А Current m 8 Z Param one 1 Zone 1 n Zone n 1 Zone Param 2 ...

Страница 15: ...nel operates in two modes DAY MODE and NIGHT MODE 3 2 5 Test indication activates a test mode allowing to perform functionality check of panel s light indication checking the functionality of the light indication of the panel 3 3 SETUP Menu to access the menu a password for access level 3 is required 3 3 1 Panel parameters the menu provides access to options for changing panel s language settings ...

Страница 16: ... functionality check on panel outputs and addressable devices outputs М9000А IO Panel outputs check is performed by manual activation of each output marked with a tick in the menu Addressable outputs check is performed by selecting the address of the device that will be tested analogically as in menu Check Address 3 3 9 Passwords allows setting a password for access level 2 and 3 Access level 2 se...

Страница 17: ...number from the available numbers at his choice 5 Assigning names to devices and adding devices to a LOOP To ensure easy orientation the fire alarm panel allows assigning an individual name to each device The devices also can be grouped in ZONES 5 1 Assigning names to devices Enter Settings menu Device Parameters Fig 11 pos 3 4 Use the arrows to see the parameters of the device To enter a text sel...

Страница 18: ... are added in this menu EXAMPLE Let s assume that devices are allocated in a building as follows 1 Automated fire detectors 10 devices on each floor A1R A1S SR MSR 2 Manual call points MCP 3 on each floor 3 Sound and light indicator S9000A 2 on each floor We assume that each device has been addressed and has an individual address point 4 Each device has a name p 5 For example the manual call point...

Страница 19: ...ON 5 2 1 Mounting 5 2 2 System elements 7 2 2 1 Front panel 7 2 2 2 Position of modules in the box 9 2 2 3 Description of main PCB 10 2 2 4 Connecting the main supply 11 2 2 5 Connecting the storge battery 11 2 3 Connecting devices 12 2 3 1 Connecting devices to a loop 12 2 3 2 Connecting devices to a conventional line 12 2 3 3 Connecting signaling devices 13 3 Program menus and settings of the fi...

Страница 20: ...Instruction manual Fire Alarm Panel FP9000A DMTech LTD 16 N Haytov Street Pleven Tel 0889992660 e mail office dmtech ltd com page 20 of 20 ISO 9001 2015 Certified Company ...

Отзывы: