XTLN/XTLN-WiFi Installation Guide
Digital Monitoring Products
9
COMPLIANCE
Central Station Burglar Alarm Units
ANSI/UL 1610
19.1 Supervision
Commercial Burglary is provided when the Check-in and Fail Time time is set to 3 minutes.
19.2 Remote Disarm
REMOTE DISARM must be programmed as NO.
19.3 Central Station
MESSAGE TO TRANSMIT programming for zones must not be set to LOCAL (L).
Household Fire Warning System
ANSI/UL 985 NFPA 72 Specifications
20.1 Bell Output Definition
The wireless siren of the panel must be programmed to operate steady on burglary alarms and temporal on
fire alarms. See the XTLN/XTLN-WiFi Programming Guide (LT-1221).
20.2 Household System
An alarm sounding device must be installed indoors so that it is clearly heard in all sleeping areas.
20.3 Wireless Supervision Time
The Zone Information Supervision Time must be 3 minutes for fire devices. See the XTLN/XTLN-WiFi
Programming Guide.
20.4 Test Frequency
The Test Frequency option must be programmed to send a report at least once every 30 days.
20.5 Wired Modules
Modules that connect to the PROG header, such as the 738Z, must not be used since the battery standby
time will be reduced below the 24 hour minimum.