XR150FC/XR550FC Series Installation Guide
Digital Monitoring Products
1
IntroductIon
Product Specifications Summary
1.1
Power Supply
Transformer Input:
Primary input: 120 Vac, 60 Hz, Secondary output: 16 Vac 56 VA
Standby Battery:
12 Vdc, 1.0 Amps Max. charging current
Auxiliary:
12 Vdc output at .5 Amp Max*
Bell Output:
12 Vdc at .7 Amp Max*
Note:
The combined Auxiliary and Bell outputs total cannot exceed 1.2 Amps with a 56 VA Transformer.
All circuits are inherent Power Limited except the red battery wire and AC terminal.
* For Commercial Fire installations, see the Compliance Listing Guide LT-1330.
1.2
Communication
• Built-in network communication to DMP Model SCS-1R and SCS-VR Receivers
• Built-in dialer communication to DMP Model SCS-1R Receivers
• Optional cellular communication to DMP Model SCS-1R and SCS-VR Receivers
• Built-in Contact ID communication to DMP Model SCS-1R Receivers
• Optional 893A Dual Phone Line Module with phone line supervision
• Can operate as a local panel
1.3
Panel Zones
Eight 1k Ohm EOL burglary zones (zones 1 to 8)
Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10)
1.4
Keypad Bus
You can connect the following supervised keypads and expansion modules to the keypad bus:
• Alphanumeric keypads
• Sixteen-, eight-, four- and/or single-zone expansion modules
• Single-zone detectors
• Access control modules
1.5
LX-Bus™
You can connect the following devices to the LX-Bus™ connections provided on the panel. See Accessory Devices
section 3.4.
• Sixteen-, eight-, four- and/or single-zone expansion modules
• Graphic annunciator modules
• Model 521LX or 521LXT Smoke Detectors with CleanMe
• Relay output expansion modules
• Model 2W-BLX or 2WT-BLX Smoke Detectors
1.6 Outputs
The XR150FC/XR550FC Series provide two Single Pole, Double Throw (SPDT) relay outputs which require the
installation of two Model 305 relays, each rated 1 Amp at 30 Vdc resistive (power limited sources only). A Model 431
Output Harness is required to use these outputs.
The XR150FC/XR550FC Series panels also provide four open collector outputs rated for 50mA each. The open
collector outputs provide ground connection for a positive voltage source. A Model 300 Output Harness is required to
use these outputs.