Digital Monitoring Products
XR150FC/XR550FC Series Installation Guide
8
InstallatIon
Primary Power Supply
5.1
Transformers and AC Power Connection
The AC connection should be completed by a licensed electrician.
Never share the Fire Alarm Control Panel circuit with any other equipment.
The XR150FC/XR550FC panel comes supplied with a 16 Vac 56 VA transformer. The 16 Vac transformer must be wired
to a dedicated unswitched 120 Vac 60 Hz circuit with at least .87A available.
Always ground the panel before applying power to any devices!
Use 18 AWG or larger for all power
connections. The panel must be properly grounded before connecting any devices or applying power. Proper
grounding protects against Electrostatic Discharge (ESD) that can damage system components.
The 16 VAC
transformer must be
wired to a dedicated
unswitched 120 VAC
60 Hz circuit with at
least .87A available
Install cover over
screw terminals after
completing connection.
WHITE
BLACK
Ground Wire
Connected
to Enclosure
GREEN/
YELLOW
GND
S
S
56 VA
Transformer
OVC
AC
1
2
3
4
5
6
7
8
10
11 12 13 14
15 16
17
18 19
9
20
21 22
23
24 25 26 27 28
+B
BELL GND
SMK GND
RED YEL GRN BLK
Z1
Z2 Z3
Z4 Z5
Z6 Z7
Z8 Z9+ Z9– Z10+ Z10–
AC
–B
GND
GND
GND
GND
K6
K7
Output 1
Output 2
J3
Phone Line
J10
Battery
Start
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1
Out2
Outputs 3-6
J11
3
4
5
6
J2
Figure 4: 56 VA Transformer Wiring