background image

867 Installation and Programming Guide   |   Digital Monitoring Products  

 

 

 

 

 

   4

ADDITIONAL INFORMATION

Wiring Specifications

DMP recommends using 18 or 22 AWG for all LX‑Bus and Keypad Bus connections. The maximum wire distance 
between any module and the DMP Keypad Bus or LX‑Bus circuit is 1,000 feet. To increase the wiring distance, install 
an auxiliary power supply, such as a DMP Model 505‑12. Maximum voltage drop between a panel or auxiliary power 
supply and any device is 2.0 VDC. If the voltage at any device is less than the required level, add an auxiliary power 
supply at the end of the circuit.

To maintain auxiliary power integrity when using 22‑gauge wire on Keypad Bus circuits, do not exceed 500 feet. 
When using 18‑gauge wire, do not exceed 1,000 feet. Maximum distance for any bus circuit is 2,500 feet regardless of 
wire gauge. Each 2,500 foot bus circuit supports a maximum of 40 LX‑Bus devices.

For additional information refer to the LX‑Bus/Keypad Bus Wiring Application Note (LT‑2031) and the 710 Bus 
Splitter/Repeater Module Installation Guide (LT‑0310).

Power Supply

The bell power must be supplied by a regulated, power limited, auxiliary power supply listed for Fire Protective 
Signaling with a maximum output of 5 Amps at 12 or 24 VDC. The power supply output positive connects to module 
Terminal 1 and power supply output negative connects to module Terminal 2.

The power supply must be supervised and provide a set of Normally Closed trouble contacts that connect to the 
Power Supply Monitor zone (Terminals 7 and 8) on the 867 module. An open on the supervision circuit causes the 
Power Supply Monitor LED to light and an open condition to be reported on the panel supervisory zone address.

LED Operation

For normal operation, all notification devices are connected in parallel on the Style W circuit. An included 10k Ohm 
EOL resistor installs at the last device in the circuit. The Style W circuit LED operation is defined as follows:

 

Normal—No LEDs light and the module reports a normal condition on the supervisory zone address.

 

Open or Short—The TRBL LED lights and the module reports an open condition on the supervisory zone 
address.

 

Ground Fault—The TRBL and GND FAULT LEDs light and the module reports an open condition on the 
supervisory zone address.

Bell Silence Switch

The Bell Silence slide switch allows technicians to test or perform maintenance on the fire system without sounding 
the fire alarm notification devices. When the switch is placed in the Bell Silence position, the module TRBL LED turns 
on and an open condition is reported on the supervisory zone address. After testing, returning the silence switch to 
the Bell Normal position returns the module to normal operation.

Отзывы: