867 Installation and Programming Guide | Digital Monitoring Products
2
INSTALLATION
1
Mount the Module
The module can be mounted in a DMP enclosure using the standard 3‑hole
mounting pattern. Refer to Figure 1 as needed during installation.
1. Hold the plastic standoffs against the inside of the enclosure side wall.
2. Insert the included Phillips head screws from the outside of the enclosure
into the standoffs. Tighten the screws.
3. Carefully snap the module onto the standoffs.
2
Address the Module
For more information about addressing and switch locations, refer to Table 1 and Figure 3 respectively.
Set the Bell Output Address
Bell Address switches allow you to set an output number for the module that can be activated by any panel zone,
fire bell output, or burglary bell output. When activated, the module provides a programmed bell output for the
duration of the bell cutoff time or until manually silenced by an authorized user.
Set the Supervisory Zone Address
Supervisory Address switches allow you to set the zone address for the module, which is programmed into the
panel as a supervisory zone. A trouble condition on the bell circuit either causes the panel to display a trouble on
the keypads or trips zone outputs and reports the trouble to the central station.
The module occupies a single zone address on the LX‑Bus. For example, on an XR550 Series panel, a module
connected to LX700 with the switches set to 5, 2 would be Supervisory Address zone number 752.
Figure 1: Standoff and Module
Installation
SWITCH
XR150 SERIES
XR550 SERIES
TENS
ONES
LX500
LX500 LX600 LX700 LX800 LX900
0
0
500
500
600
700
800
900
0
1
501
501
601
701
801
901
0
2
502
502
602
702
802
902
0
3
503
503
603
703
803
903
0
4
504
504
604
704
804
904
...
...
...
...
...
...
...
...
9
5
595
595
695
795
895
995
9
6
596
596
696
796
896
996
9
7
597
597
697
797
897
997
9
8
598
598
698
798
898
998
9
9
599
599
699
799
899
999
Table 1: LX-Bus Addresses