Digital Monitoring Products, Inc. | 714N-POE Installation and Programming Guide
11
PANEL IP PORT
Enter the port number that the module uses to send communication
to the panel. This must be the same port that is programmed in
the 714N-POE Listen Port in Network Options programming of the
panel. The panel IP port cannot be the same as the panel network
programming port. Default is
2002
.
714N-POE PASSPHRASE
You must enter an 8-16 character alphanumeric passphrase to encrypt
communication with the panel. The passphrase for the 714N-POE
must match the 734N passphrase entered in Network Options
programming of the panel. If no 734N has been installed, a passphrase
is still required for the 714N-POE to communicate with the panel. The
passphrase is blank by default.
PANEL IP PORT
2002
734N
PASSPHRASE