6050-065-D-2-16
19
3.2 DIP-Switch SW 3 & SW 4 Settings
The two DIP-switches located on the circuit board are used to program the operator to operate in various modes and to turn on
or off various operating features. Whenever a switch setting is changed, power to the operator must be turned OFF and then
turned back on for the new setting to take affect. Check and review ALL switch settings prior to applying power to the operator.
Switch
Function
Setting
Description
SW 4 (Top 8 Switches)
OFF
ON
OFF
ON
OFF
OFF
ON
1-OFF
1-OFF
1-ON
1-ON
2-OFF
2-ON
2-OFF
2-ON
Auto-Close
Timer
Not Used
Dual Operators
Single Operator
Circuit
Board
Relay
3
4
5
7
1 and 2
Auto-close timer is OFF. Manual input required to close gate.
Auto-close timer is ON. Adjustable from 1-23 seconds to close gate.
Leave in the OFF position.
OFF
ON
3-Button
Single Button
6
OFF when using a 3-button station (DoorKing 3-button control stations only).
ON when using a single button control, terminals 13 &14 become a STOP input.
Switch must be OFF when bi-parting (dual) gates are used.
Switch must be ON for single operator.
OFF
ON
Tamper Protect
8
Tamper protect is OFF.
Normal Setting.
Tamper protect is ON. Operator will close gate when being forced open.
Relay activates when gate is open (Shadow loop setting when used).
Relay activates when gate is not closed.
Relay activates when gate is opening and open.
Relay activates when gate is opening and closing.
The output wired to terminal #12 becomes the output from the exit loop detector plugged
into the EXIT Loop port.
Normal Setting.
Terminal #12 is a normal full open input.
Exit Loop Port
Output
Full Open Input
Every time
the operator is powered up, the
First
open command
will
automatically set the open and close limits of the gate.
(See page 21).
OFF
ON
Reverse
Shadow Loop
Terminal 15 is a STANDARD Reverse input.
Terminal 15 is a Shadow input. Gate will
NOT
stop
during
the close cycle.
Switch
Function
Setting
Description
SW 3 (Bottom 8 Switches)
Secondary
Gate Opening
Direction
OFF
ON
Motor Control
for Secondary
Operator
Primary
Gate Opening
Direction
2
3
4
6
7
8
1
Switch is OFF when both primary and secondary operator motors are powered from main
terminals 4 and 5. Applies to operators originally manufactured with 4501, Rev O boards or
lower).
Switch is ON when secondary operator motor is powered from the secondary motor
terminals. Applies to operators manufactured with 4501, Rev P boards and higher,
and all
4502 boards.
5
Gate Overlap
OFF
ON
OFF
ON
OFF
ON
Primary and secondary operators start at the same time.
Secondary operator starts 1-2 seconds prior to primary operator.
Same as above, for secondary 6050/6100
ONLY
.
ON
OFF
Opens
Clockwise
Opens
Counter-Clockwise
OFF
Not Used
Leave in OFF position.
Monitored
Edge/Beam
No Photo Sensor connected to Aux terminal 7 and 8.
Photo sensor is connected to Aux terminal 7 and 8 and monitored. (Close ONLY)
No Edge or Beam connected to Aux terminal 9 and 10.
Edge OR Beam is connected to Aux terminal 9 and 10 and monitored. (Open/Close)
Monitored
Close Beam