1. Important 

Information 

 

This manual contains important safety and operating instructions and specifications for DKS Model 
1000 Inverter / Backup Power System. This manual is the property of the owner of the equipment and 
must be left in their possession after the installation of the product is complete. 

SAVE THESE 

INSTRUCTIONS! 

 

The 1000 Watt Inverter (1000-080) can be used to power a single, 1/2 HP gate operator system 
when in continuous duty mode, or can be used with two (2) 1/2 HP gate operators when open 
upon power failure mode is used. 

The 1500 Watt Inverter (1000-081) can be used to power a bi-parting, 1/2 HP gate operator 
system; or it can be used to power a single, 1 HP gate operator system.

 

 

The DKS Model 1000 Power Inverter uses a modified sine wave as the AC output.  Because of 
this, vehicular gate operators that use a current sensor device (ERD) as an inherent 
entrapment protection system may experience false entrapment inputs when the inverter 
powers the gate operator.  DKS gate operators that use an ERD have been specifically 
designed to work within the limits of the modified sine wave

 

2. Important 

Precautions 

 

 

CAUTION

 – The Model 1000 produces lethal voltages.  It should be installed by a qualified 

electrician and operated with care and attention.  The batteries are capable of supplying 
hazardous current.  Follow the instructions carefully. 

 

CAUTION

 – 

Risk of Energy Hazard, 12 V, 35 Ampere-hour battery.  

Dangerous voltages 

are present even when the AC is off.  Remove personal metal items such as rings, bracelets, 
necklaces, and watches when working with electrical circuits. These items can cause a short-
circuit current high enough to weld a ring, or the like, to metal causing severe burns. 

 

CAUTION

 – Disconnect the charging source prior to connecting or disconnecting the 

batteries.  Do not install or connect batteries to this unit until instructed to do so. Failure to 
comply with this instruction can cause damage or complete failure of the inverter unit. 

 

CAUTION

 - To reduce risk of injury, use only the type of batteries specified.  

Maintenance-

Free, Rechargeable, Nonspillable, Sealed Lead-Acid (SLA), 12-Volt, 35.0 AH.

 

 

BATTERIES MUST HAVE SCREW TYPE TERMINALS.  DO NOT USE BATTERIES WITH 
CLAMP TYPE TERMIANLS. 

 

CAUTION

 – Do not dispose of batteries in a fire.  The battery may explode.  Batteries should 

be taken to a recycling center. 

 

CAUTION

 – Do not open or mutilate the batteries.  Released electrolyte is harmful to skin 

and eyes.  It is toxic. 

 

Never charge a frozen battery. 

  Someone should be within range of your voice to come to your aid when you work near 

batteries. 

 

NEVER smoke or allow a spark or flame in vicinity of the batteries. 

  Be extra cautious when working with metal tools on and around batteries. Use tools with 

insulated handles.  Do not lay tools or metal parts on top of the batteries.  The potential exists 
to short-circuit the batteries or other electrical parts that may result in a spark that could 
cause an explosion. 

 

 

Page 6 

 

1000-065-B-7-09 

Содержание 1000-080

Страница 1: ...wer Backup Systems Owner s Manual DoorKing Inc 120 Glasgow Avenue Inglewood California 90301 U S A Phone 310 645 0023 Fax 310 641 1586 www doorking com P N 1000 065 REV B 7 09 Copyright 2001 DoorKing...

Страница 2: ...Page 2 1000 065 B 7 09...

Страница 3: ...manual without notice and without obligation of DoorKing Inc to notify any persons of any such revisions or changes Additionally DoorKing Inc makes no representations or warranties with respect to th...

Страница 4: ...Page 4 1000 065 B 7 09...

Страница 5: ...Specifications 8 4 Mounting 9 5 Read Before Wiring 10 6 Wiring Instructions 10 7 LED Status Indicators 12 8 Battery Test and Reset Push Buttons 12 9 Switch Settings Terminal Description 14 10 Status r...

Страница 6: ...gy Hazard 12 V 35 Ampere hour battery Dangerous voltages are present even when the AC is off Remove personal metal items such as rings bracelets necklaces and watches when working with electrical circ...

Страница 7: ...e parts inside this unit are energized from the battery supply even when AC power is disconnected CAUTION Risk of electrical shock AC Input and AC Output terminals can be energized even with AC INPUT...

Страница 8: ...tput Wave Form Modified Sine Wave DC Input Voltage 10 15 VDC Low Battery Alarm 10 5 VDC 5 V 1000 080 9 5 VDC 5 V 1000 081 Low Battery Shutdown 9 5 VDC 5 V Frequency 60 Hz Efficiency 90 No Load Current...

Страница 9: ...alled The system operates best when it can be installed as physically close as possible to the equipment that it is intended to operate during power outages This reduces line loss The effective capaci...

Страница 10: ...Y A SNAP THIS IS NORMAL DON T LET IT SCARE YOU WARNING Never disconnect the batteries while the system is delivering power or the battery charger is operating Always turn the system OFF first 6 Wiring...

Страница 11: ...perator 1 open terminals relay 2 Term 9 10 to gate operator 2 open terminals Connect 115 VAC source voltage to AC input terminals Connect RED wire from J1 to POSITIVE terminal on battery Connect BLACK...

Страница 12: ...ng a trickle charge to it to maintain the full charge TEMP RED LED indicates that the battery is not being charged because the temperature is outside the battery safe operating range 23 F 4 C to 126 F...

Страница 13: ...RESET BATT TEST INPUT AC POWER OUTPUT AC POWER HRT BEAT DIAGNOSTIC UTIL OPER INV ON B BAD B OK BULK TRICK TEMP SHDN 110V ON 1000 065 B 7 09 Page 13...

Страница 14: ...er a shut down condition When primary AC Utility power is lost the system will provide AC power to the gate operator s until the battery is too weak to continue operation At this time the system will...

Страница 15: ...1000 065 B 7 09 Page 15 1 2 3 4 5 6 7 8 9 10 RESET J2 J3 J6 J4 J8 J1 BATT TEST INPUT AC POWER OUTPUT AC POWER HRT BEAT DIAGNOSTIC UTIL OPER INV ON B BAD B OK BULK TRICK TEMP SHDN 110V ON...

Страница 16: ...l change see status report table below Status Report Table ASCII Character Hex Value Description 0 30 AC failure detected 1 31 AC present detected 2 32 System switched to battery operation 3 33 System...

Страница 17: ...2 Volt 35 AH Battery and Cable Assembly Order this to add a second battery to the 1000 Watt inverter system 1801 005 12 Volt 35 AH replacement battery 1000 044 Battery Cables 2355 010 Circuit Board 05...

Отзывы: