10. Status
Report
The Model 1000 Inverter has a status report function that can be downloaded to a PC using a DB-9
connector and the RS-232 Serial port (refer to the table on page 14 for DB-9 wire connections). This
feature can be used for troubleshooting purposes. The Model 1000 communicates at 300 baud, 8
data bits, no parity, 1 stop bit. A byte will be sent per functional change (see status report table
below).
Status Report Table
ASCII
Character
Hex
Value
Description
0
30 AC
failure
detected
1
31
AC present detected
2
32
System switched to battery operation
3
33
System switched to AC operation
4
34
System shut down because of low battery
5
35
Battery test initiated by timer
6
36
Battery test initiated by push button
7
37 Battery
tested
good
8
38 Battery
tested
weak
9
39 Battery
tested
bad
:
3A
Battery charge failed because of bad battery
;
3B
Battery charge ended good
<
3C
Temperature outside of operating range
Page 16