Switch Settings / Terminal Description 

 

Switch Settings (

settings in

 bold 

are default settings

SW # 

Description 

OFF 

ON 

Low Battery 
Shutdown 

HIGH – Shutdown occurs at a higher 
battery voltage.  Use with heavier 
gates. 

LOW – Shutdown occurs at a lower battery 
voltage.  Use with two battery systems 
and/or lighter gates. 

Battery 
Test 

Battery Test OFF. 

Battery test automatically every few days to 
determine battery condition. 

Number of 
Batteries 

Two (2) batteries. 

One (1) battery. 

Beep Alert 

Beep Alert is OFF. 

Beeps every 30 seconds when battery 
charging has failed or the board is in a 
shutdown condition. 

Relay 
Activation on 
AC Power 
Loss 

When primary AC (Utility power) is 
lost – relays will activate immediately 
to open gate, then the system will 
enter a shut down condition. 

When primary AC (Utility power) is lost – 
the system will provide AC power to the 
gate operator(s) until the battery is too 
weak to continue operation.  At this time, 
the system will activate each relay 
individually 55 seconds apart, and then 
shut down. 

Low Battery 

When battery is too weak to sustain 
operation – system shuts down. 

When battery is too weak to sustain 
operation – activate relay to open gate then 
shut down. 

Relay 
Activation on 
AC Power 
Restore 

Relays are not activated. 

Relays activate for 1/2-sec. when primary 
AC (Utility power) returns or when board 
powers up from a shutdown condition. 

Not Used 

N/ A 

Leave this switch in the ON position. 

 

Terminals (J4) 

No. Description 

RS-232 Serial Data (D9 – Pin 2) 

RS-232 Busy (D9 – Pin 4) 

RS-232 Ground (D9 – Pin 5) 

Signal Ground (not earth ground) 

Not Used 

Not Used 

Relay 1 Normally Open 

Relay 1 Common 

Relay 2 Normally Open 

10 

Relay 2 Common 

 

 

 

 

 

Page 14 

 

1000-065-B-7-09 

Содержание 1000-080

Страница 1: ...wer Backup Systems Owner s Manual DoorKing Inc 120 Glasgow Avenue Inglewood California 90301 U S A Phone 310 645 0023 Fax 310 641 1586 www doorking com P N 1000 065 REV B 7 09 Copyright 2001 DoorKing...

Страница 2: ...Page 2 1000 065 B 7 09...

Страница 3: ...manual without notice and without obligation of DoorKing Inc to notify any persons of any such revisions or changes Additionally DoorKing Inc makes no representations or warranties with respect to th...

Страница 4: ...Page 4 1000 065 B 7 09...

Страница 5: ...Specifications 8 4 Mounting 9 5 Read Before Wiring 10 6 Wiring Instructions 10 7 LED Status Indicators 12 8 Battery Test and Reset Push Buttons 12 9 Switch Settings Terminal Description 14 10 Status r...

Страница 6: ...gy Hazard 12 V 35 Ampere hour battery Dangerous voltages are present even when the AC is off Remove personal metal items such as rings bracelets necklaces and watches when working with electrical circ...

Страница 7: ...e parts inside this unit are energized from the battery supply even when AC power is disconnected CAUTION Risk of electrical shock AC Input and AC Output terminals can be energized even with AC INPUT...

Страница 8: ...tput Wave Form Modified Sine Wave DC Input Voltage 10 15 VDC Low Battery Alarm 10 5 VDC 5 V 1000 080 9 5 VDC 5 V 1000 081 Low Battery Shutdown 9 5 VDC 5 V Frequency 60 Hz Efficiency 90 No Load Current...

Страница 9: ...alled The system operates best when it can be installed as physically close as possible to the equipment that it is intended to operate during power outages This reduces line loss The effective capaci...

Страница 10: ...Y A SNAP THIS IS NORMAL DON T LET IT SCARE YOU WARNING Never disconnect the batteries while the system is delivering power or the battery charger is operating Always turn the system OFF first 6 Wiring...

Страница 11: ...perator 1 open terminals relay 2 Term 9 10 to gate operator 2 open terminals Connect 115 VAC source voltage to AC input terminals Connect RED wire from J1 to POSITIVE terminal on battery Connect BLACK...

Страница 12: ...ng a trickle charge to it to maintain the full charge TEMP RED LED indicates that the battery is not being charged because the temperature is outside the battery safe operating range 23 F 4 C to 126 F...

Страница 13: ...RESET BATT TEST INPUT AC POWER OUTPUT AC POWER HRT BEAT DIAGNOSTIC UTIL OPER INV ON B BAD B OK BULK TRICK TEMP SHDN 110V ON 1000 065 B 7 09 Page 13...

Страница 14: ...er a shut down condition When primary AC Utility power is lost the system will provide AC power to the gate operator s until the battery is too weak to continue operation At this time the system will...

Страница 15: ...1000 065 B 7 09 Page 15 1 2 3 4 5 6 7 8 9 10 RESET J2 J3 J6 J4 J8 J1 BATT TEST INPUT AC POWER OUTPUT AC POWER HRT BEAT DIAGNOSTIC UTIL OPER INV ON B BAD B OK BULK TRICK TEMP SHDN 110V ON...

Страница 16: ...l change see status report table below Status Report Table ASCII Character Hex Value Description 0 30 AC failure detected 1 31 AC present detected 2 32 System switched to battery operation 3 33 System...

Страница 17: ...2 Volt 35 AH Battery and Cable Assembly Order this to add a second battery to the 1000 Watt inverter system 1801 005 12 Volt 35 AH replacement battery 1000 044 Battery Cables 2355 010 Circuit Board 05...

Отзывы: