26
• Device is C2 class with fan and it is hermetic. This device can also be
used in accordance with B2 class (only exhaust gases are expulsed).
For this purpose, it is required to have air connection as shown in Figure
1.3.1. Suitable grilles must be installed for air intake.
• Device is manufactured with double telescopic pipe in C2 connection (80
cm is provided with the product) suitable for direct outlet, vertical outlet
and parallel separated outlet connections. Maximum chimney lengths
for these connections are provided in Figure 1.3.2 – 1.3.3 – 1.3.4. In
equivalent length calculations, each 90˚ elbow shall be considered as
1 m and added accordingly.
1.3. Chimney Connection
Figure 1.3.1
Figure 1.3.2
Maximum equivalent length: 6 m
Figure 1.3.3
Maximum equivalent length:15 m
Figure 1.3.4
Maximum equivalent length: 20 m