1592001850 XC660D GB r3.4 04.09.2017.docx XC660D
53/
55
Label
Valori
Menù
Descrizione Parametri
Limiti
-999÷999(KPA)
inC
500
Pr2
Integral time, suction 1
0 ÷ 999 sec
2Pbd
5.0
Pr2
Proportional band for compressors
regulation, suction 2
0.1÷30.0(°C); 1÷50 (°F); 0.1÷10.0(BAR);
1÷150(PSI) 10÷1000(KPA)
2rS
0.0
Pr2
Band offset, suction 2
-12.0÷12.0(°C) -20÷20(°F)
-12.0÷12.0(BAR); -200÷ 200(PSI)
-999÷999(KPA)
2inC
500
Pr2
Integral time, suction 2
0 ÷ 999 sec
ton
60
Pr2
Time with Inverter at maximum capacity
before starting a new load
0÷255s
toF
30
Pr2
Time with Inverter at minimum capacity
before starting a new load
0÷255s
ESC
0.0
Pr1
Energy saving for compressors regulation
-50.0÷50.0(°C) -90÷90(°F)
-20.0÷20.0(BAR) -300÷300(PSI)
-2000÷2000(KPA)
2ESC
0.0
Pr1
Energy saving for compressors regulation,
circuit 2
-50.0÷50.0(°C) -90÷90(°F)
-20.0÷20.0(BAR) -300÷300(PSI)
-2000÷2000(KPA)
OnOn
5
Pr2
Minimum delay between 2 switching on of the
same compressor
0 ÷ 255 (min.)
OFOn
1
Pr2
Delay between the switching off and on of the
same compressor
0 ÷ 255 (min.)
don
01:00
Pr2
Time delay between the insertion of two
different loads
0 ÷ 99.5 (min.10sec)
doF
00:30
Pr2
Time delay between switching off of two
different compressors
0 ÷ 99.5 (min.10sec)
donF
1:00
Pr2
Minimum time a stage stays ON
0 ÷ 99.5 (min.10sec)
MAon
0
Pr2
Maximum time a stage stays switched ON
0 ÷ 24 (hour)
FdLy
no
Pr2
'don' delay enabled also for the first request
no - yES
FdLF
no
Pr2
'doF' delay enabled also for the first switching
off
no - yES
odo
20
Pr2
Regulation delay at power on
0 ÷ 255 (sec.)
LSE
-40.0
Pr2
Minimum set point (compressors)
-50.0÷HSE(°C) -58.0÷HSE(°F)
PA04÷HSE(BAR,PSI,KPA)
HSE
10.0
Pr2
Maximum set point (compressors)
LSE÷150.0(°C) LSE÷302(°F)
LSE÷PA20(BAR , PSI , KPA)
2LSE
-40.0
Pr2
Minimum set point compressors, for circuit 2
-50.0÷2HSE(°C) -58.0÷2HSE(°F)
3P04÷2HSE(BAR,PSI,KPA)
2HSE
10
Pr2
Maximum set point compressors for circuit 2
LSE÷150.0(°C) LSE÷302(°F)
LSE÷3P20(BAR , PSI , KPA)
Lit
90.0
Pr2
Set point for liquid injection
0.0 ÷ 180.0°(°C) 32 ÷ 356(°F)
Lid
10.0
Pr2
Differential for liquid injection
0.1 ÷ 25.5° (°C) 1 ÷ 50° (°F)
LiPr
nP
Pr2
Probe selection for liquid injection
nP - P3 - P4
Pb
5.0
Pr2
Proportional band for fan regulation
0.1÷30.0(°C) 1÷50 (°F) 0.1÷10.0(BAR)
1÷150(PSI) 10÷1000(KPA)
ESF
0.0
Pr2
Energy saving differential for fan regulation
-50.0÷50.0(°C) -90÷90(°F)
-20.0÷20.0(BAR) -300÷300(PSI)
-2000÷2000(KPA)
PbES
0.0
Pr2
Band offset for fan regulation in ES
-50.0÷50.0(°C) -90÷90(°F)
-20.0÷20.0(BAR) -300÷300(PSI)
-2000÷2000(KPA)
Fon
30
Pr2
Time delay between the insertion of two
different fan
0 ÷ 255 (sec)
FoF
15
Pr2
Time delay between switching off of two
different fan
0 ÷ 255 (sec)
LSF
10.0
Pr2
Minimum set point (fan)
-50.0÷HSF(°C) -58.0÷HSF(°F)
FA04(FPb)÷HSF(BAR , PSI , KPA)