1592001850 XC660D GB r3.4 04.09.2017.docx XC660D
23/
55
Plant with 3 compressors
suction 1 , 3 compressors
suction 2, with inverter for
fans:
oA1 = CPr1,
oA2 = CPr1,
oA3 = CPr1,
oA4 = CPr2,
oA5 = CPr2,
oA6 = CPr2,
AOC = tEn
AOF = InF
CtyP
Compressor type:
it sets if compressors have the same power (homogeneous) or not.
SPo
=
compressors with same capacity
dPo
=
compressor with different capacities
.
Scr = screw compressors.
StP
Valve outputs (unloader) polarity:
polarity of the outputs for capacity valves. It
determines the status of the relays associated with the capacity valves (only for
homogeneous and stepped-capacity compressors)
oP
=valve activated with open contacts of the relay;
cL
= valve activated with close contacts of the relay.
PC1..PC6
Capacity of compressor 1...6:
for setting the capacity of single compressors.
It’s
used only if CtyP=dPo.
Insert in each parameter the capacity of the compressor used.
E.I.
3 compressors with following capacity: 10, 20, 40 HP. The parameters have to be set
in this way: PC1=10, PC2=20, PC3=40.
FtyP
:
Refrigerant type
: set the kind of gas refrigerant used in the plant:
LABEL
REFRIGERANT
OPERATING RANGE
R22
r22
-50-60°C/-58÷120°F
r134
r134A
-70-60°C/-94÷120°F
r404A
r404A
-50-60°C/-58÷120°F
r407A
r407A
-50-60°C/-58÷120°F
r407C
r407C
-50-60°C/-58÷120°F
r407F
r407F
-50-60°C/-58÷120°F
r410
r410
-50-60°C/-58÷120°F
r507
r507
-70-60°C/-94÷120°F
CO2
r744 - Co2
-50-30°C/-58÷86°F
r32
r32
-70-60°C/-94÷120°F
r290
r290
– Propane
-50-60°C/-58÷120°F
r448
r448A
-45-60°C/-69÷120°F
r449
r449A
-45-60°C/-69÷120°F
r450
r450A
-45-60°C/-69÷120°F
r513
r513
-45-60°C/-69÷120°F