1592025700 IPROFAMILY stp GB 2012.08.08.doc
iPro Series
49/72
116
RL17
SSR relay 17 normally open contact
117
RL18
SSR relay 18 normally open contact
118
RL19
SSR relay 19 normally open contact
119
P
Common SSR relays 16, 17, 18 and 19
120
RL24
Relay 24 normally open contact
121
P
Common relays 24 and 25 (MAX 6A)
122
RL25
Relay 25 normally open contact
4.7.3 Technical
specifications
4.7.3.1 Analogue inputs
Analogue conversion type:
10-bit A/D converter
Number of inputs:
10
Type of analogue input:
(configurable via software parameter)
NTC Dixell (-50T110°C; 10K
Ω
±1% at 25°C)
PTC Dixell(-55T115°C; 990
Ω
±1% at 25°C)
PT1000 Dixell (-100T150°C; 1K
Ω
at 0°C)
Digital input (potential free contact)
Voltage: 0 - V, 0 - 5V, 0 - 10V (input resistance 15K
Ω
)
Current: 0 - 20mA, 4 - 20mA (input resistance 100
Ω
)
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Accuracy:
NTC, PTC, PT1000: ±1°C
0-1V: ±20mV
0-5V: ±100mV
0-10V:±200mV
2-20mA, 4-20mA: ±0.30mA
Additional power:
+12V: 200mA max
+5v: 100mA
Notes:
Any inputs that are powered with a voltage that differs from that supplied
by the device (+12V or +5V) must be powered separately with another
transformer (do not use the same secondary of the controller's power) in
order to prevent the inputs from malfunctioning or being damaged.
4.7.3.2 Digital inputs
Type:
(configurable via software parameter)
Opto-insulated potential free or live contact (24Vac/dc)
External power 24Vac/dc ±20%
Number of inputs:
20
Digital input status variation detection time:
100ms (in any case it depends on the cycle time set by the user in the
given application)
Notes:
If the digital inputs are used with voltage, use another transformer (do not
use the same secondary of the controller's power) in order to prevent the
inputs from malfunctioning or being damaged.
4.7.3.3 Analogue outputs
Type:
Opto-insulated with separate 24Vac/dc power supply
Number of outputs:
6
Type of analogue output:
(configurable via software parameter)
4 fixed outputs 0-10Vdc (Out1 - Out4)
2 configurable outputs 0-10Vdc, 4-20mA (Out5 and Out6)
Maximum load:
40mA (Out1 - Out4)
20mA (Out5 and Out6) max with configured outputs 0-10Vdc
400
Ω
max with configured outputs 4-20mA
22
Ω
per live analogue output
Accuracy:
Out1 - Out4: ±2% full scale
Out5 – Out6: ±2% full scale
Resolution:
8bit
Notes:
The electrical devices controlled by these analogue outputs must be
powered separately with another transformer (do not use the same
secondary of the controller's power) in order to prevent the outputs from
malfunctioning or being damaged.
Содержание iPro SERIES
Страница 1: ...iPro SERIES V 3 2 ...
Страница 2: ......
Страница 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...
Страница 20: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 20 72 4 2 IPRO GENIUS IPG200D RANGE ...
Страница 54: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 54 72 5 1 4 Dimensions ...
Страница 72: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 72 72 ...