1592025700 IPROFAMILY stp GB 2012.08.08.doc
iPro Series
47/72
Digital relay outputs
4 NO relays, 1 common
Digital relay outputs
2 NO relays, 1 common
Green power LEDs (PWR ON) and red alarm signal LED (ALARM)
See relative paragraph
4.7.2
Description of the inputs and outputs
Input
No.
Type of Input
Description
1 Supply
Reference “-“/GND power (24Vac or 24Vdc)
2 Pb1
Configurable analogue input 1 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
3 Pb2
Configurable analogue input 2 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
4 Pb3
Configurable analogue input 3 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
5 Pb4
Configurable analogue input 4 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
6 Pb5
Configurable analogue input 5 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
7
PbC
Common analogue inputs (NTC, PTC, PT1000, DI)
8 GND(-)
Additional power reference 5Vdc and 12Vdc and analogue inputs (0 - 20mA, 4 - 20mA, 0 -
10V, 0 - 1V, 0 - 5V)
9 Supply
Reference “+“ power supply (24Vac or 24Vdc)
10 Pb6
Configurable analogue input 6 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
11 Pb7
Configurable analogue input 7 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
12 Pb8
Configurable analogue input 8 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
13 Pb9
Configurable analogue input 9 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
14 Pb10
Configurable analogue input 10 (NTC, PTC, PT1000, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 -
5V, DI)
15 +5V
Additional
power
+5Vdc
16 +12V
Additional
power
+12Vdc
21
Out1
Opto-insulated analogue output 1 0 - 10V
22
Out2
Opto-insulated analogue output 2 0 - 10V
23
Out3
Opto-insulated analogue output 3 0 - 10V
24
Out4
Opto-insulated analogue output 4 0 - 10V
25
GND(-)
Common opto-insulated analogue output
26
Out5
Analogue output 5 0 - 10V, 4 - 20mA, Opto-insulated relay
27
Out6
Analogue output 6 0 - 10V, 4 - 20mA, Opto-insulated relay
28
Supply
Power for opto-insulated analogue outputs at 24Vac or 24Vdc(-)
29
Supply
Power for opto-insulated analogue outputs at 24Vac or 24Vdc(+)
30
GND(-)
Common opto-insulated analogue output
40
DI1
Opto-insulated digital input 1
41
DI2
Opto-insulated digital input 2
42
DI3
Opto-insulated digital input 3
43
DI4
Opto-insulated digital input 4
44
DI5
Opto-insulated digital input 5
45
DI6
Opto-insulated digital input 6
46
DI7
Opto-insulated digital input 7
47
DI8
Opto-insulated digital input 8
Содержание iPro SERIES
Страница 1: ...iPro SERIES V 3 2 ...
Страница 2: ......
Страница 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...
Страница 20: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 20 72 4 2 IPRO GENIUS IPG200D RANGE ...
Страница 54: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 54 72 5 1 4 Dimensions ...
Страница 72: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 72 72 ...