1592025700 IPROFAMILY stp GB 2012.08.08.doc
iPro Series
28/72
24Vac/dc digital inputs (DI1 - DI11, GND)
Connector for remote terminal (VISOGRAPH), maximum 1 terminal per iPRO.
RS485 Slave connector
Serial port connector (LAN or RS485)
USB port for downloads (BIOS, ISaGRAF® application, maps of parameters, remote display
applications, network configuration, website) and uploads (log files)
Connection with the computer via a USB-ETH converter
Digital relay outputs
4 NO relays, 2 common
Digital relay outputs
4 NO relays, 2 common
4.3.2
Description of the inputs and outputs
Input
No.
Type of Input
Description
1 Supply
Reference “-“/GND power (24Vac or 24Vdc)
2
Pb1
Configurable analogue input 1 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
3
Pb2
Configurable analogue input 2 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
4
Pb3
Configurable analogue input 3 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
5 +12V
Additional
power
+12Vdc
6 +5V
Additional
power
+5Vdc
7
Out1
Analogue output 1 0 - 10V, 4 - 20mA, Relay
8
Out2
Analogue output 2 0 - 10V, 4 - 20mA, Relay
9 Supply
Reference “+“ power supply (24Vac or 24Vdc)
10
Pb4
Configurable analogue input 4 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
11
Pb5
Configurable analogue input 5 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
12
Pb6
Configurable analogue input 6 (NTC, PTC, 0 - 20mA, 4 - 20mA, 0 - 10V, 0 - 1V, 0 - 5V, DI)
13
PbC
Common analogue inputs (NTC, PTC, DI)
14 GND(-)
Additional power reference 5Vdc and 12Vdc, analogue inputs (0 - 20mA, 4 - 20mA, 0 - 10V, 0
- 1V, 0 - 5V), analogue outputs
15
Out3
Analogue output 3 0 - 10V, 4 - 20mA, Relay
16
Out4
Analogue output 4 0 - 10V, 4 - 20mA, Relay
20
DI1
Digital input 1 24Vac/dc
21
DI2
Digital input 2 24Vac/dc
22
DI3
Digital input 3 24Vac/dc
23
DI4
Digital input 4 24Vac/dc
24
DI5
Digital input 5 24Vac/dc
25
DI6
Digital input 6 24Vac/dc
26
DI7
Digital input 7 24Vac/dc
27
DI8
Digital input 8 24Vac/dc
28
DI9
Digital input 9 24Vac/dc
29
DI10
Digital input 10 24Vac/dc
30
DI11
Digital input 11 24Vac/dc
31 GND(-)
Reference “-“ for digital inputs from1 to 11 (if version with dry contacts, this input has
to be used only as common for the digital inputs)
40
C
Common relays 1, 2, 3 and 4 (MAX 10A)
41
C
Common relays 1, 2, 3 and 4 (MAX 10A)
42
RL1
Relay 1 normally open contact
43
RL2
Relay 2 normally open contact
Содержание iPro SERIES
Страница 1: ...iPro SERIES V 3 2 ...
Страница 2: ......
Страница 18: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 18 72 4 1 3 6 Wiring diagrams ...
Страница 20: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 20 72 4 2 IPRO GENIUS IPG200D RANGE ...
Страница 54: ...1592025700 IPROFAMILY stp GB 2012 08 08 doc iPro Series 54 72 5 1 4 Dimensions ...