1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 69 of 149
Parameter
Description
min
max
udm
US 47
Probe 1 selection for evaporator water pump modulation in chiller
0
10
US 48
Probe 2 selection for evaporator water pump modulation in chiller
0
10
US 49
Set point for maximum speed of modulationg evaporator water pump in chiller
30.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 50
Proportional band for maximum speed of modulationg evaporator water pump
in chiller
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 51
Minimum speed of the evaporator water pump in chiller
0
100
%
US 52
Maximum speed of the evaporator water pump in chiller
0
100
%
Heat pump and sanitary hot water
Parameter
Description
min
max
udm
US 53
Probe 1 selection for evaporator water pump modulation in Heat Pump
0
10
US 54
Probe 2 selection for evaporator water pump modulation in Heat Pump
0
10
US 55
Set point for maximum speed of modulationg evaporator water pump in Heat
Pump
30.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
US 56
Proportional band for maximum speed of modulationg evaporator water pump
in Heat Pump
0.0
0
0.0
0
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
US 57
Minimum speed of the evaporator water pump in Heat Pump
0
100
%
US 58
Maximum speed of the evaporator water pump in Heat Pump
0
100
%
32. WATER PUMP OF THE CONDENSER
Condenser Water pump control
Water pump operation mode:
CO21=0:
Not enabled: water pump is not managed.
CO21 = 1:
Continuous control
The water pump is ON only if the unit is running (chiller or heat pump).