1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 35 of 149
1. Keep pushed SET key;
2. Push 1 time the DOWN key and the leds 3 is off, the parameter is now available also in Pr2.
To show the parameter only in Pr3:
1. Keep pushed SET key
2. Push 1 time the DOWN key and the leds 3 and 4 are off, the parameter is now available only in Pr3.
Visibility and Parameter value locked
To set the only visibility and lock the parameter value it is necessary enter Pr3 programming level.
Pr1 PARAMETER VISIBILITY
Enter the Pr3 level
1. Select the parameter;
2. Keep pushed the SET key;
3. Push 1 time the MENU key and the led 3 change from on to blinking: the parameter is visible in Pr1 but
can’t be changed.
Pr2 PARAMETER VISIBILITY
Enter the Pr3 level
1. Select the parameter;
2. Keep pushed the SET key;
3. Push 1 time the MENU key and the led 4 change from on to blinking the parameter is visible in Pr2 but
can’t be changed.
Leds 3 / 4 blinking:
the parameter is visible in Pr1 and in Pr2 but in those levels now they can’t be
changed.
TO SET THE ORIGINAL TAG FOR THE PARAMETER Pr1 / Pr2
1.
Keep pushed the
SET
key;
2.
Push one time the
MENU
key, the leds 3 / 4 turn on, the parameter can be seen and modified in Pr1 and Pr2.
Programming: digital input and output polarity
The parameters that allow to configure different options such as:
1. Digital inputs
2. Digital outputs (relay)
3. Proportional output configured as ON/OFF
4. Analogue input configured as digital input
have a different parameter description that allows to configure the operating mode and the corresponding
polarity.
Example of programming:
The bottom display shows the parameter label (CF36) Digital input ID1 configuration;
Note that the top display shows
“c”
or
“o”
before the configuration number.
The selection
7
for the digital input ID1 (CF36) means that it is the “high pressure switch of circuit 1”.
The label “
o”
means that the digital input is active for
open
contact.
Otherwise if the selection is
7
for the digital input ID1 (CF36) = “high pressure switch of circuit 1”.
The label “
c”
means that the digital input is active for
closed
contact.
Change the polarity of the digital Inputs-Outputs
Enter the programming:
1. Select a parameter with digital input/output value, The top display shows the label
o
before the
configuration number while the bottom display shows the parameter label.