1592015820 User manual IC260_261L_D DUO FW1.9 rel. 1.0
Pag. 61 of 149
Parameters involved:
CO60
Operation time at CO61 power when the compressor inverter
controlled is switched on
0
250
sec
CO61
Forced power when the compressor inverter controlled is
switched on
0
100
%
CO62
Delay to increase the power during the start up phase of the
compressori inverter controlled
1
250
sec
CO63
Compressor inverter controlled operation power under whitch
start counting CO64 time
0
100
%
CO64
Maximun operation time of the compressor inverter controlled
with power less than CO63
0
250
Min
10 Min
CO65
Operating time of the compressor inverter controlled at
maximum power
0
250
sec
10sec
CO66
Maximum operating time of the compressor inverter controlled
0
999
Hr
1Hr
CO67
Minimum value of the compressor 1 inverter controlled
0
CO68
%
CO68
Maximum value of the compressor 1 inverter controlled
CO67
100
%
CO69
Minimum value of the compressor 2 inverter controlled
0
CO70
%
CO70
Maximum value of the compressor 2 inverter controlled
CO69
100
%
CO71
Delay to increase/decrease the power of the compressori
inverter controlled
1
250
sec
...
CO79
Maximum speed of the inverter compressors in chiller
1
100
%
CO80
Maximum speed of the inverter compressors in heat pump
1
100
%