IC70CX
Pag. 20 of 23
n = no: compressor keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case
regulation restarts after C02 time at minimum
A08 Compressor and heater off with boiler high temperature alarm:
n = no: compressor keeps on working; Y = yes, compressor is switched off till the alarm is present, in any case
regulation restarts after C02 time at minimum
A09 Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time interval between the detection of the
temperature alarm condition after instrument power on and alarm signalling.
A10 Probe selection for temperature alarm 2: nP = no probe; P1 =thermostat probe; P2 = evaporator probe; P3
=configurable probe; P4 = Probe 4.
A11 Set point low temperature alarm 2: (-55÷150°C) when this temperature is reached the LA2 alarm is signalled,
possibly after the A14 delay
A12 Set point high temperature alarm 2: (-55÷150°C) when this temperature is reached the HA2 alarm is signalled, after
the A14 delay.
A13 Differential for temperature 2: (0,1÷25,5°C; 1÷45°F).
A14 Termperature alarm 2 delay: (0÷255 min) time interval between the detection of the condenser alarm condition and
alarm signalling.
A15 Temperature alarm exclusion at start up: (from 0.0 min to 23.5h, res. 10min).
A16 Compressor and heater off with low temperature alarm of boiler: n = no: compressor and heater keep on working;
Y = yes, compressor and heater are switched off till the alarm is present, in any case regulation restarts after C02 time
at minimum.
A17 Compressor and heater off with high temperature alarm of condenser: n = no: compressor and heater keeps on
working; Y = yes, compressor and heater are switched off till the alarm is present, in any case regulation restarts after
C02 time at minimum.
A18 Alarm relay silencing:
n= silencing disabled: alarm relay stays on till alarm condition lasts,
y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm.
A19 (0
255 min)
with C15= EAL or C15 = bAL digital input alarm delay: delay between the detection of the external alarm condition
and its signalling.
with C15 = PAL: time for pressure switch function: time interval to calculate the number of the pressure switch
activation.
A20 Pressure switch number: (0
15) Number of activation of the pressure switch, during the “A19” interval, before
signalling the alarm event (C15= PAL)
If the A20 activation in the did time is reached, switch off and on the instrument to restart normal regulation.
A21 Alarm relay polarity