IC70CX
Pag. 16 of 23
C 11
Pb1 Regulation probe calibration
-12,0°C ÷ 12,0°C
-21°F ÷ 21°F
0,1°C / 1°F
C 12
Pb2 Evaporator probe calibration
-12,0°C ÷ 12,0°C
-21°F ÷ 21°F
0,1°C / 1°F
C 13
Pb3 probe calibration
-12,0°C ÷ 12,0°C
-21°F ÷ 21°F
0,1°C / 1°F
C 14
Pb4 probe calibration
-12,0°C ÷ 12,0°C
-21°F ÷ 21°F
0,1°C / 1°F
C 15
Digital input 1 configuration
EAL(0) - bAL(1) -
PAL(2) - onF(3)
-
C 16
Digital input 1 polarity
OP(0) - CL(1)
-
C 17
Second relay configuration
dEF(0) - FAn(1) -
ALr(2) - AUS(3) -
OnF(4) - HEt(5)
-
C 18
Third relay configuration
dEF(0) - FAn(1) -
ALr(2) - AUS(3) -
OnF(4) - HEt(5)
-
C 19
Fourth relay configuration
dEF(0) - ALr(1)
-
C 20
Not used
C 21
Not used
C 22
Not used
C 23
Firmware Release (only reading)
C 24
Map code (only reading)
C 25
Serial address
1 ÷ 247
C 26
Kind of action for auxiliary relay
CL(0) - Ht(1)
C 27
Set point of auxiliary relay
-55.0°C ÷ 150,0°C
-67°F ÷ 302°F
C 28
Differential of auxiliary relay
0,1°C ÷ 25,5°C
1°F ÷ 45°F
C 29
Auxiliary relay status during defrost
n(0) - Y(1)
C 30
Probe selection for auxiliary relay
nP(0) - P1(1) - P2(2) -
P3(3) - P4(4)
C 31
Probe 1 value (only visualization)
(probe value)
C 32
Probe 2 value (only visualization)
(probe value)
C 33
Probe 3 value (only visualization)
(probe value)
C 34
Probe 4 value (only visualization)
(probe value)
d01
Defrost selection
EL(0) - in(1)
-
d02
Defrost end temperature
-55.0°C ÷ 50.0°C
-67°F ÷ 122°F
1°C / 1°F
d03
Interval between defrost cycles
0 ÷ 255 (ore)
1 hour
d04
Interval between defrost cycles time resolution
Hur(0) - Min(1)
-
d05
Maximum duration of the defrost
0 ÷ 255 (min.)
1 minute
d06
Start defrost delay
0 ÷ 255 (min.)
1 minute
d07
Draining time
0 ÷ 255 (min.)
1 minute
d08
Visualization during defrost
rt(0) - it(1) - SEt(2) -
dEF(3)
-
F 01
Fan operating mode
C_n(0) - O_n(1) -
C_Y(2) - O_Y(3)
-
F 02
Fan stop temperature
-55.0°C ÷ 50.0°C
-67°F ÷ 122°F
1°C / 1°F
F 03
Fan delay after defrost
0 ÷ 255 (min.)
1 minute