IC70CX
Pag. 18 of 23
rtC Real time clock menu: to set the time and date and defrost start time.
TO SET CURRENT TIME AND WEEKLY HOLIDAYS
Hur
Current hour (0 ÷ 23 h)
Min
Current minute (0 ÷ 59min)
dAY Current day of the week (Sun ÷ SAt)
REGULATION
S01 Set point Regulation set point (S3
S04)
S02 Differential (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point
S03 Minimum Set Point: (- 50°C÷C01/-58°F÷C01): Set the minimum value for set point
S04 Maximum Set Point: (S01÷110°C/ S01÷230°F). Set the maximum value for set point.
S05 Set point resistance for integration to compressor Set point activation of the resistance as integration to the
compressor
S06 Differential resistance for integration to compressor (0,1°C
25,5°C): Differential for resistence regulation as
integration to the compressor
S07 Resistance activation delay: delay to switch on the resistence
S08 Set point resistance on evaporator probe: Set point for resistance activation
S09 Differential resistance on evaporator probe: Differential for resistance regulation
S10 Set point to switch off compressor on evaporator probe: Set point to switch off the compressor if evaporator
temperature falls below a determined temperature
S11 Differential to switch on compressor on evaporator probe: Differential of compressor de-activation
S12 Set point for anti legionella cycle: Set point of the anti legionella cycle
S13 Time to reach anti legionella set point: maximum time to reach the anti-legionella set point
S14 Anti legionella cycle at start-up; this parameter allow to enable the anti legionella cycle at the power on
S15 Antilegionella start time; hour of anti legionella cycle activation
S16 Antilegionella duration; the anti legionella temperature has to be maintained for this time;
S17 Day to activate anti legionella cycle; day of anti legionella cycle activation
COMPRESSOR
C01 Outputs activation delay at start up: (0÷255 min) This function is enabled at the initial start up of the instrument and
inhibits any output activation for the period of time set in the parameter.
C02 Anti-short cycle delay: (0÷50 min) minimum interval between compressor stop and following restart.
C03 Compressor ON time with faulty probe: (0÷255 min) time during which the compressor is active in case of faulty
thermostat probe. With CO3=0 compressor is always OFF.
C04 Compressor OFF time with faulty probe: (0÷255 min) time during which the compressor is OFF in case of faulty
thermostat probe. With CO4=0 compressor is always active.
CONFIGURATION
C05 Type of probe: (Ptc = probe PTC; ntc= probe NTC).
C06 Temperature measurement unit: °C = Celsius; °F = Fahrenheit.
When the measurement unit is changed, temperature set point and hysteresis have to be checked and modified if
necessary.
C07 Resolution (only for °C): (in = 1°C; dE = 0.1 °C) allows decimal point displaying.
C08 Evaporator probe presence (P2): (n = Not present: defrost stops by time; y = present: defrost stops by temperature).
C09 Pb3 probe presence
C10 Pb4 probe presence
C11 Pb1 Thermostat probe calibration: (-12.0
12.0°C) allows to adjust reading value of thermostat probe
C12 Pb2 Evaporator probe calibration (P2): (-12.0
12.0°C) allows to adjust reading value of evaporator probe
C13 Pb3 probe calibration
C14 Pb4 probe calibration
C15 Digital input configuration:
EAL = signalling alarm; bAL = alarm to stop the machine; PAI = pressure switch alarm; onF = remote ON/OFF
C16 Digital input polarity: oP= the digital input is activated by opening the contact. CL= the digital input is activated by
closing the contact.
C17 Second relay configuration (
dEF - FAn – ALr - AUS - OnF- HEt)
C18 Third relay configuration (
dEF - FAn – ALr - AUS - OnF- HEt)