3 PHASE ELECTRICAL WIRING DIAGRAM
Standard 115v unit comes wired to a toggle switch with 15 ft cord, see figure 5 above. 230 V single phase units
are factory wired to a junction box on the side of the cabinet, switch not included. Additional wiring will be required
to get power to unit, which is not supplied with this product. Three phase units are wired to a junction box on the
motor, see figure 4 above.
Motor Starters, disconnects, wiring, overloads and thermal protection are NOT provided by the Manufacturer.
All Field wiring should be performed by a qualified electrician and must meet all local, NFPA and NEC codes.
Failure to install the proper electrical wiring, thermal protection, and controls will void the warranty.
ROTATION
- On single phase units motor rotation can be reversed by switching the black and red leads in the
motor. Three phase motors can be reversed by switching leads L1 and L2. VERIFY rotation before operating the
air cleaner to avoid over amping the motor, voiding warranty.
After completion of the field wiring, turn the unit on to check for proper rotation. Rotation is marked on the side
of the blower housing for the standard forward curve blower. Optional direct drive BI blower wheels will rotate in
a clockwise direction when looking at the top of the motor, or the wheel should be spinning from right to left as
viewed through the exhaust grid. Backward rotation will result in a much lower air flow, louder noise, and will over
amp the motor. Check the motor nameplate before switching wires and reversing rotation, to ensure the unit is
operating at or below rated full load amp draw. Figure 6 illustrates how to identify the proper rotation.