2.3 – Power supply and connectors
CN1
1 2
1
2
WIRING and POWER SUPPLY RANGE
MICRA-D
85 V – 265 V AC 50/ 60 Hz or 100 – 300 V DC
MICRA-D6
22 – 53 V AC 50/ 60 Hz or 10,5 - 70 V DC
Borne 1: Phase
Borne 2: Neutral
NOTE: When DC power supply (direct) polarity
in connector CN1 is indistinct.
WARNING: If not installed and used in accordance with these
instructions, protection against hazards may be impaired.
In order to guarantee the electromagnetic compatibility, the following
guidelines should be kept in mind:
-
Power supply wires may be routed separated from signal wires.
-
Never run power and signal wires in the same conduit.
-
Use shielded cable for signal wiring and connect the shield to the ground.
-
The cables section should be
>
0.25 mm
2
INSTALLATION
To meet the requirements of the directive EN61010-1, where the unit is
permanently connected to the mains supply, it is obligatory to install a circuit
breaking device easy reachable to the operator and clearly marked as the
disconnect device.
CONNECTORS
CN1
To perform wiring connections, strip the wire leaving from 7 and 10 mm
exposed to air and insert it in the proper terminal while pushing the fingertip
down to open the clip inside the connector as indicated in the figures.
Each terminal accepts cables of section between 0.08 mm² and 2.5 mm² (AWG
26 ÷ 14).
11
11
2.3 – Power supply and connectors
CN1
1 2
1
2
WIRING and POWER SUPPLY RANGE
MICRA-D
85 V – 265 V AC 50/ 60 Hz or 100 – 300 V DC
MICRA-D6
22 – 53 V AC 50/ 60 Hz or 10,5 - 70 V DC
Borne 1: Phase
Borne 2: Neutral
NOTE: When DC power supply (direct) polarity
in connector CN1 is indistinct.
WARNING: If not installed and used in accordance with these
instructions, protection against hazards may be impaired.
In order to guarantee the electromagnetic compatibility, the following
guidelines should be kept in mind:
-
Power supply wires may be routed separated from signal wires.
-
Never run power and signal wires in the same conduit.
-
Use shielded cable for signal wiring and connect the shield to the ground.
-
The cables section should be
>
0.25 mm
2
INSTALLATION
To meet the requirements of the directive EN61010-1, where the unit is
permanently connected to the mains supply, it is obligatory to install a circuit
breaking device easy reachable to the operator and clearly marked as the
disconnect device.
CONNECTORS
CN1
To perform wiring connections, strip the wire leaving from 7 and 10 mm
exposed to air and insert it in the proper terminal while pushing the fingertip
down to open the clip inside the connector as indicated in the figures.
Each terminal accepts cables of section between 0.08 mm² and 2.5 mm² (AWG
26 ÷ 14).