Sensor Input Type

Input Connection Diagram

ECL‑300, ECL‑400, and ECL‑600 Series:

£

0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by the controller’s internal
15VDC power supply.

£

For jumper location, see 

Jumper Identification and Configuration [pg. 6]

.

+

-

Sensor

0-20mA

Controller 

0-20mA Input 

Equivalent 

Circuit

UIx

COM

To Analog-

To-Digital 

Converter

249

Jumper 

Setting

0-10V

0-20mA

+15VDC

ECL‑300, ECL‑400, and ECL‑600 Series:

£

0  to  20mA  input  used  with  a  2-wire,  0  to  20mA  sensor  powered  by  an  external  24VDC
power supply.

£

For jumper location, see 

Jumper Identification and Configuration [pg. 6]

.

-

+

Sensor

0-20mA

Controller 

0-20mA Input 

Equivalent 

Circuit

UIx

COM

To Analog-

To-Digital 

Converter

249

Jumper 

Setting

0-10V

0-20mA

24VDC

ECL‑300, ECL‑400, and ECL‑600 Series:

£

0  to  20mA  input  used  with  a  3-wire,  0  to  20mA  sensor  powered  by  an  external  24VAC
power supply.

£

For jumper location, see 

Jumper Identification and Configuration [pg. 6]

.

AC

+

Common

Sensor

0-20mA

Controller 

0-20mA Input 

Equivalent 

Circuit

UIx

COM

To Analog-

To-Digital 

Converter

249

Jumper 

Setting

0-10V

0-20mA

24VAC

ECL‑300, ECL‑400, and ECL‑600 Series:

£

0 to 20mA input used with a sensor powered by its own power source.

£

For jumper location, see 

Jumper Identification and Configuration [pg. 6]

.

+

-

Sensor

0-20mA

Controller 

0-20mA Input 

Equivalent 

Circuit

UIx

COM

To Analog-

To-Digital 

Converter

249

Jumper 

Setting

0-10V

0-20mA

£

Voltage input used with a 3-wire 0 to 10VDC or 0 to 5VDC sensor powered by an external
24VAC power supply.

AC

+

Common

0-10V

Sensor

UIx

COM

To Analog-

To-Digital 

Converter

24VAC

£

Voltage  input  used  with  a  0  to  10VDC  or  0  to  5VDC  sensor  powered  by  its  own  power
source.

+

-

0-10V

Sensor

UIx

COM

To Analog-

To-Digital 

Converter

£

Slow  Pulse  –  Internal  supply:  2-wire  pulse  meter  for  ECL‑203,  ECL‑300,  ECL‑400,  and
ECL‑600 Series controllers

£

Connect  the  pulse  input  according  to  the  figure  for  a  pulse  meter  that  can  pull-down  a
+5VDC supply with a 10KΩ pull-up resistor (internal supply type).

£

Refer to Table 1 for more information on Controller Input Support

Pulse Meter 
Output

Controller 

Pulse Input 

Equivalent 

Circuit

UIx or DIx

COM

To Pulse Count 

Accumulator

+

-

10K

5VDC

£

Fast Pulse – Internal supply: 2-wire pulse meter for ECL‑300, ECL‑400, and ECL‑600 Series
controllers

£

Connect  the  pulse  input  according  to  the  figure  for  a  pulse  meter  that  requires  more  than
5VDC to operate using built in controller power source from 6VDC to 15VDC maximum.

£

Refer to Table 1 for more information on Controller Input Support

Pulse Meter 
Output

Controller

15VDC

COM

+

-

Suitable current-limiting resistor as 

recommended by the pulse meter’s 

manufacturer (field supplied)

UI1 to UI4

To Pulse Count Accumulator

Trigger Threshold: 2.5Volts

23.5k

Equivalent Load

£

Fast Pulse – External supply: 2-wire pulse meter for ECL‑300, ECL‑400, and ECL‑600 Se-
ries controllers

£

Connect  the  pulse  input  according  to  the  figure  for  a  pulse  meter  that  requires  more  than
5VDC to operate using an external power source from 6VDC to 27VDC maximum.

£

Refer to Table 1 for more information on Controller Input Support

Pulse Meter 
Output

Controller

COM

To Pulse Count Accumulator

Trigger Threshold: 2.5Volts

+

-

Suitable current-limiting 

resistor as recommended 

by the pulse meter’s 

manufacturer (field supplied)

Power Source

6 to 27VDC Max.

UI1 to UI4

23.5k

Equivalent Load

Table 2: Input Wiring

Содержание LonWorks ECL-203 Series

Страница 1: ...of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before installation to allow any condensa...

Страница 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Страница 3: ...3 16 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Страница 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Страница 5: ...the secondary side of the transformer Connecting the power source to Electrical System Ground is not a requirement for proper system operation However it is good installation practice to do so in ord...

Страница 6: ...e 0 20 mA Enable LONWORKS Network Board Net to Subnet Settings Enabled Disabled Figure 9 ECL 300 Controller Jumper Locations Factory default positions LONWORKS Network Board Universal Outputs UO 0 10V...

Страница 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Страница 8: ...24VAC Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECL...

Страница 9: ...WM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECL 300 ECL...

Страница 10: ...e Protect the controller s connector from being pulled on when a cable to the Allure Series is connected Create a strain relief by looping the cable and attaching it to a solid object with a nylon tie...

Страница 11: ...o the Troubleshooting Guide The Cat5e cable length is restricted by the maximum allowable subnetwork bus length see the Allure EC Smart Vue Hardware Installation Guide for more information Controller...

Страница 12: ...sed to relieve tension on the wiring and conceal the controllers wire terminals Strain reliefs and terminal block covers are optional and are sold as peripherals Prior to connecting all wires it is re...

Страница 13: ...its are designed to provide reasonable protection against harmful interference in a residential and commercial installation This equipment generates uses and can radiate radio frequency energy and if...

Страница 14: ...ormer 24VAC 4A Fuse Fast Acting EOL Enabled at the last sensor at the end of the Bus From Previous Device To Next Device L ON W ORKS Network 249 ohm resistor built in for inputs configured as 4 20mA E...

Страница 15: ...Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers See Power Wiring Network not wired properly Double check that the wire connections are corre...

Страница 16: ...t Short Short blink 800ms On 300ms Off 150ms On 300ms Off 150ms On 300ms Off 150ms On The controller is in bypass mode Appropriate action Set the controller Online Short Short Long blink 150ms On 300m...