Device too far from the Wireless Receiver

Reposition the device to be within the range of the Wireless Receiver. For information on typical transmission ranges, refer
to the 

Open-to-Wireless Application Guide.

Configuration problem

Using  the  device  configuration  plug-in  or  wizard,  check  the  configuration  of  the  input.  Refer  to  the  Wireless  Battery-less
Sensors and Switches Solutions Guide for more information.

Rx/Tx LEDs

RX LED not blinking

Data is not being received from the 

L

ON

W

ORKS

 

data bus.

TX LED not blinking

Data is not being transmitted onto the 

L

ON

W

ORKS

 

data bus.

Status LED– Normal Operation

One fast blink

Initialization: The device is starting up.

Fast blink continuous:

(150ms On, 150ms Off, continuous)

Firmware  upgrade  in  progress.  Controller  operation  is  temporarily  unavailable.  The  new  firmware  is  being  loaded  into
memory. This takes a few seconds. Do not interrupt power to the device during this time.

The Status LED is always OFF

The controller is operating normally.

Status LED blink patterns – Repeats every 2 seconds (highest priority shown first)

Long blink continuous:

(1s On, 1s Off, continuous)

The controller is not commissioned.

Appropriate action: Commission the controller.

Long Long Long blink

(800ms  On,  300ms  Off,  800ms  On,  300ms  Off,
800ms On)

The controller is offline.

Appropriate action: Set the controller Online

Long Short Short Short blink

(800ms  On,  300ms  Off,  150ms  On,  300ms  Off,
150ms On, 300ms Off, 150ms On)

The controller is in bypass mode.

Appropriate action: Set the controller Online

Short Short Long blink

(150ms  On,  300ms  Off,  150ms  On,  300ms  Off,
800 ms On)

Poor-quality  power;  The  device  has  browned-out:  The  voltage  at  the  24VAC  and  24VCOM  terminals  has  gone  below  the
device’s acceptable limit during power up.

Fast blink 12x:

(80ms On, 80ms Off, 12x)

Wink. The wink function is used to identify a device.

For issues with the Allure EC-Smart-Vue Series Communicating Sensor, refer to the Allure EC-Smart-Vue Series Communicating Sensor Hardware In-
stallation Guide.

©, Distech Controls Inc., 2012 - 2019. All rights reserved.

Images are simulated. While all efforts have been made to verify the accuracy of information in this manual, Distech Controls is not responsible for damages or claims arising from the use of this manual.

Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail-safe environ-

ments. Distech Controls reserves the right to change, delete or add to the information in this manual at any time without notice.

Distech Controls, the Distech Controls logo, Open-to-Wireless, Innovative Solutions for Greener Buildings, and Allure are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE.

Global Head Office - 4205 place de Java, Brossard, QC, Canada, J4Y 0C4 - EU Head Office - ZAC de Sacuny, 558 avenue Marcel Mérieux, 69530 Brignais, France

Содержание LonWorks ECL-203 Series

Страница 1: ...of the device pay special attention to the following recommendations It is recommended that the controller s be kept at room temperature for at least 24 hours before installation to allow any condensa...

Страница 2: ...e Hardware Installation Guide Alternating Current Direct Current General Wiring Recommendations Risk of Electric Shock Turn off power before any kind of servicing to avoid electric shock All wiring mu...

Страница 3: ...3 16 Controller Dimensions Components Figure 2 Rear view of large enclosure Figure 3 Rear view of small enclosure Figure 4 Side view of large and small enclosure...

Страница 4: ...orientation must be horizontal with controller s back attached to a vertical wall surface Figure 5 Permitted Mounting Positions DIN Rail Mounted Installation 1 Ensure the DIN rail is properly mounted...

Страница 5: ...the secondary side of the transformer Connecting the power source to Electrical System Ground is not a requirement for proper system operation However it is good installation practice to do so in ord...

Страница 6: ...e 0 20 mA Enable LONWORKS Network Board Net to Subnet Settings Enabled Disabled Figure 9 ECL 300 Controller Jumper Locations Factory default positions LONWORKS Network Board Universal Outputs UO 0 10V...

Страница 7: ...6 Table 1 Controller Input Support Sensor Input Type Input Connection Diagram Dry Contact input UIx COM To Digital Input Digital Dry Contact NO NC RTD input for example 1000 Thermistor Input for examp...

Страница 8: ...24VAC Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its own power source 0 10V Sensor UIx COM To Analog To Digital Converter Slow Pulse Internal supply 2 wire pulse meter for ECL...

Страница 9: ...WM output controlling a 12VDC relay Maximum 60 mA minimum load resistance 200 UOx From Digital Output 12VDC Relay A1 A2 UOx COM Current 0 to 20mA universal output jumper configuration For ECL 300 ECL...

Страница 10: ...e Protect the controller s connector from being pulled on when a cable to the Allure Series is connected Create a strain relief by looping the cable and attaching it to a solid object with a nylon tie...

Страница 11: ...o the Troubleshooting Guide The Cat5e cable length is restricted by the maximum allowable subnetwork bus length see the Allure EC Smart Vue Hardware Installation Guide for more information Controller...

Страница 12: ...sed to relieve tension on the wiring and conceal the controllers wire terminals Strain reliefs and terminal block covers are optional and are sold as peripherals Prior to connecting all wires it is re...

Страница 13: ...its are designed to provide reasonable protection against harmful interference in a residential and commercial installation This equipment generates uses and can radiate radio frequency energy and if...

Страница 14: ...ormer 24VAC 4A Fuse Fast Acting EOL Enabled at the last sensor at the end of the Bus From Previous Device To Next Device L ON W ORKS Network 249 ohm resistor built in for inputs configured as 4 20mA E...

Страница 15: ...Overloaded power transformer Verify that the transformer used is powerful enough to supply all controllers See Power Wiring Network not wired properly Double check that the wire connections are corre...

Страница 16: ...t Short Short blink 800ms On 300ms Off 150ms On 300ms Off 150ms On 300ms Off 150ms On The controller is in bypass mode Appropriate action Set the controller Online Short Short Long blink 150ms On 300m...

Отзывы: