13
DischargeHumiditySensorAlarm_1
MSV
26
Discharge Humidity
Sensor Alarm [MSV
Enumerated]
Y
DischargeHumiditySensorAlarm_2
MSV
27
Discharge Humidity
Sensor Alarm [MSV
Enumerated]
Y
ReheatBurnerLockoutAlarm
MSV
28
Reheat Burner Lockout
Alarm [MSV
Enumerated] (unit was
commanded on for 2
minutes and fan motor
did not start)
Y
DirtyFinalFitlerAlarm
MSV
4
Dirty Filter Alarm [MSV
Enumerated]
Y
OutsideHumiditySensorAlarm 1
MSV
8
Return Temp Sensor
Alarm [MSV
Enumerated]
Y
MotorNotRespondingAlarm 1
MSV
10
Motor Not Responding
Alarm [MSV
Enumerated] (unit was
commanded on for 2
minutes and fan motor
did not start)
Y
FanCommand
BV
8
Fan Command
(enumerated 0=Off /
1=On)
Y
UnitDesignCFM
AV
10
Unit Design CFM (used
when airflow
monitoring and control
not available)
Y
ManualVFDSpeedPercent
AV
11
Manual VFD Speed Set
Point (overrides
automatic VFD control /
use 'null' value for
automatic control)
Y
UnitInstallationAltitude
AV
12
Altitude in Feet Above
Sea Level at which the
unit is installed
Y