12
DischargeSensorCount
BV
6
Number of Discharge
Temp/Humidity Sensors
Available
Y
AirflowAvailable
BV
7
Airflow (DFM)
Monitoring and Control
Available
Y
DischargeeTempSetPoint
AV
5
Discharge Temperature
Set Point
Y
DischargeHumiditySetPoint
AV
6
Discharge Humidity Set
Point
Y
DischargeAirflowSetPoint
AV
7
Discharge Airflow (DM)
Set Point
Y
PreHeatBurnerReset
AV
8
Preheat Burner Reset
Command
Y
ReheatBurnerReset
AV
9
Reheat Burner Reset
Command
Y
OutsideTemperature
AV
36
Outside Temperature
Y
OutsideHumidity
AV
37
Outside Air Humidity
Y
CoilExitTemperature
AV
38
Coil Exit Temperature
Y
PreheatExitTemperature
AV
39
PreheatExitTemperature
Y
DischargeTemperature
AV
40
Discharge Air
Temperature
Y
DischargeHumidity
AV
41
Discharge Humidity
Y
DischargeAirflowCFM
AV
42
Discharge Airflow CFM
Y
CoolingCommand
AV
43
Cooling Command
Precent
Y
PreheatCommand
AV
44
Preheat Command
Percent
Y
HumiditficationCommand
AV
45
Humidification
Command Percent
Y
ReheatCommand
AV
46
Reheat Command
Percent
Y
DirtyFinalFilterAlarm
MSV
21
Dirty Filter Alarm [MSV
Enumerated]
Y
CoilExitTempSensorAlarm
MSV
22
Coil Exit Sensor Alarm
[MSV Enumerated]
Y
PreheatTempSensorAlarm
MSV
23
Preheat Sensor Alarm
[MSV Enumerated]
Y
DischargeTempSensorAlarm_1
MSV
24
Discharge Temp Sensor
Alarm [MSV
Enumerated]
Y
DischargeTempSensorAlarm_2
MSV
25
Discharge Temp Sensor
Alarm [MSV
Enumerated]
Y