11
DischargeSensorAlarm
MSV
3
Discharge Temp Sensor
Alarm [MSV
Enumerated]
Y
OutsideTempSensorAlarm
MSV
5
Outside Temp Sensor
Alarm [MSV
Enumerated]
Y
OutsideHumiditySensorAlarm
MSV
6
Outside Humidity
Sensor Alarm [MSV
Enumerated]
Y
PreheatBurnerLockoutAlarm
MSV
7
Burner Lockout Alarm
[MSV Enumerated]
Y
MotorNotRespondingAlarm
MSV
9
Motor Not Responding
Alarm [MSV
Enumerated] (unit was
commanded on for 2
minutes and fan motor
did not start)
Y
Reheat Burner ON
BI
13
Reheat Burner ON
Contact
Y
Reheat Burner Lockout
BI
14
Reheat Burner Lockout
Contact
Y
Dirty Pre-Filter Switch
BI
15
Dirty Pre-Filter Switch
Contact
Y
Dirty Final Filter Switch
BI
16
Dirty Final Filter Contact
Y
Humidity_PID
LOOP
2
Humidity Control PID
Y
PreHeat_PID
LOOP
3
Preheat Control PID
Y
ReHeat_PID
LOOP
4
Reheat Control PID
Y
Airflow PID
LOOP
5
Airflow Control PID
Y
LowTempAlarmSetPoint
AV
1
Low Temp Alarm Set
Point
Y
LowTempAlarmTime
AV
2
Low Temp Alarm Time
(minutes)
Y
MinimumDischargeTemp
AV
3
Minimum Discharge
Temperature
Y
MaximumDischargeTemp
AV
4
Maximum Discharge
Temperature
Y
DirtyPreFilterSwitchAvail
BV
1
Dirty Pre-Filter Switch
Available
Y
DirtyFinalFilterSwitchAvail
BV
2
Dirty Final Filter Switch
Available
Y
HumidificationAvailable
BV
3
Humidification Available
Y
HumidificationType
BV
4
Humidification Type
(EVAP/STEAM)
Y
ReHeatAvailable
BV
5
Reheat Available
Y