Subnet Wiring 

The subnet is used to connect a range of Allure Series Communicating 

Sensors: 

The  Allure EC-Smart-Vue Series Communicating  Sensor  is a 

communicating room temperature sensor with backlit display 

graphical menus and VAV balancing capabilities.  

The  Allure  EC-Smart-Comfort and Allure EC-Smart-Air 

Communicating  Sensors  are  a  range of communicating room 

temperature sensors. 

Connect the Allure  Series  Communicating Sensor  to the controller’s 

Subnet Port

 with a standard Category 5e Ethernet patch cable fitted 

with RJ-45 connectors.  The  Network Guide  provides extensive 

information and requirements for the connection of the  Allure  Series 

Communicating Sensor. It contains information about network topology 

and  length, cable type, setting the Subnet ID, etc. It can be 

downloaded  from our  website.  See also the Hardware Installation 

Guide supplied with the Allure Series Communicating Sensor. 
The ECL-VAV model supports the connection of EC-Multi-Sensor 

series, ECx-Light series, and ECx-Blind series to the 

Subnet Port

 as 

part of the Smart Room Control (see the controller’s datasheet for 

more  information). See the room device calculator spreadsheet 

available for download from our website to know the permitted 

quantities: 

VAV- Smart Room Control Device Calculator.xlsm

 

If you make your own patch cable, see the Allure Series 

Communicating Sensor Hardware Installation Guide. 

 

Protect the controller’s connector from being pulled on when 

a cable to the Allure Series Communicating Sensor  is 

connected. Create a strain-relief by looping the cable and 

attaching it to a solid object with a nylon tie so that a tug on 

the cable will not pull out the connector on the controller. 

Communications Wiring 

The recommended cable type for L

ON

W

ORKS

®

  communications is 

22AWG (0.65 mm), twisted pair, unshielded. The L

ON

W

ORKS

 

communication wire is polarity insensitive and can be laid out in a bus, 

star, loop or free topology. For loop topology, polarity is important, 

special care must be taken when connecting the L

ON

W

ORKS

 network 

to avoid short circuit. 

 

It is recommended to use the bus topology network 

configuration for all LonWorks  communication wiring, as it 

allows for easy network troubleshooting. 

 

Connect both wires to the LON+ and LON- terminals of the controller. If 

inserting multiple wires in the terminals, ensure to properly twist wires 

together prior to inserting them in the terminal connectors. 

Controller 2 

      

Controller 1 

LON+

LON-

LON+

LON-

LON Network

To Next Controller

 

Figure 10:  

Communications Wiring 

For more information and detailed explanations on network topology 

and wire length restrictions, refer to the Network Guide. It can be 

downloaded from our website. 

 

It is important to use proper network terminators depending 

on the type of network topology used. Failure to do so might 

result in communication errors between controllers. 

Selecting Network Terminators 

Topology 

Distech Controls Part # 

Bus 

PDIDI-BT-TP10XX 

Free 

PDIDI-FT-TP10XX 

 
For a bus topology, 2 network terminators are required (1 at each end 

of the bus topology channel). For a free topology, 1 network terminator 

is required and it can be put anywhere on the channel. 
When used with an Allure EC-Smart-Vue Communicating Sensor, the 

network can be accessed at the sensor’s audio plug port for 

commissioning and maintenance purposes,  when the two 

Net to 

Subnet Port Settings

 jumpers inside the ECL series controller are set 

to 

Enable 

(for jumper location, see Figure  9). This will connect the 

main L

ON

W

ORKS

 network to the subnet Cat5e cable.  

 

Recommendation

: Only a limited number of controllers on a

 

L

ON

W

ORKS

  network  segment should  have their 

Net to 

Subnet Port Settings

 jumpers enabled. Enabling too many 

Allure EC-Smart-Vue  sensors with network access may 

cause network communication issues. If there are any 

network 

communication 

problems, refer to the 

Troubleshooting Guide

. 

 

The Cat5e cable length is  restricted by the maximum allowable 

subnetwork bus length (see the Allure  EC-Smart-Vue Hardware 

Installation Guide for more information). 

Controller

Bus Network Topology: 22AWG (0.65mm) Unshielded Twisted Pair Network Cable

Cat5e communications cable:

• 

Allure EC-Smart-Vue Sub-Network Bus

• 

L

ON

W

ORKS

 Network when 

Net to Subnet 

Port Settings

 jumpers are Enabled

E

D

Enable

Disable

For a Few 

Controllers ONLY:

Standard Net to 

Subnet Port 

Settings:

DISABLED

 - this 

is the factory 

default setting

Communicating 

Sensor

Net to Subnet Port Settings 

Optionally 

Enabled

 

Figure 11:  

L

ON

W

ORKS

 Network Bus Topology 

Wireless Installation 

When connected to a Wireless Receiver, controllers can receive input 

signals from a wide selection of wireless devices. Compatible wireless 

devices include temperature sensors, duct sensors, window/door 

contacts and light switches. These devices are easy to install, and can 

be mounted on a wide range of building materials.  

 

Before connecting any wireless equipment to the controller, 

refer to the Open-to-Wireless Solution Guide. 

Connecting the Wireless Receiver 

The Wireless Receiver is connected to the controller using a 2m (6.5ft) 

telephone cable with 4P4C modular connectors at both ends. Do not 

exceed this cable length. The Wireless Receiver’s telephone socket is 

located inside the device. To locate it, open the Wireless Receiver by 

separating its front and back plates. 

 

Figure 12:  

Location of the Wireless Receiver’s telephone socket 

Содержание ECL-103

Страница 1: ...ure during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged controllers Avoid areas where corroding deteriorating...

Страница 2: ...3 wire voltage and current inputs and outputs as well as triac outputs should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires The board connectors accep...

Страница 3: ...urn the controller s shaft coupler until it touches the mechanical end stop to either the fully closed position 90 boxes or the fully open position 45 and 60 boxes 6 For 90 VAV boxes If the damper clo...

Страница 4: ...wires when daisy chaining devices Use a wire nut with a pig tail to make such a connection Use an external fuse on the 24VAC side secondary side of the transformer as shown in Figure 8 to protect all...

Страница 5: ...COM To Analog To Digital Converter Potentiometer 10k 0 to 20mA input used with a 2 wire 0 to 20mA sensor powered by the controller s internal 15VDC power supply Sensor 0 20mA UIx COM 15VDC To Control...

Страница 6: ...UOx COM Linear 0 to 10VDC digital to analog output UOx 0 10V Common From Digital To Analog Output UOx COM 0 to 10VDC voltage output controlling an analog actuator that is powered by an external 24VAC...

Страница 7: ...network topology and wire length restrictions refer to the Network Guide It can be downloaded from our website It is important to use proper network terminators depending on the type of network topolo...

Страница 8: ...evices are not to be thrown away in municipal waste Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive North American Emissions Complian...

Страница 9: ...Heating Floating Actuator LONWORKS Network Back of Allure EC Smart Vue Wireless Port beneath cover E D E D Service PIN Button BAC LON Figure 14 Typical Power and Network Connections with an Allure EC...

Страница 10: ...rcuit shows approximately 0V DC and an open circuit shows approximately 5V DC Configuration problem Using EC gfxProgram check the configuration of the input Refer to the controller s user guide for mo...

Страница 11: ...eats every 2 seconds highest priority shown first Long blink continuous 1s On 1s Off continuous The controller is unconfigured Appropriate action Commission the controller Long Long Long blink 800ms O...

Страница 12: ...VAC specialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change...

Отзывы: