background image

 

4/12 

 

Daisy-chaining controllers is not permitted when a controller’s 

expected power consumption including external loads is over 15VA. In 

this case the controller must be connected to the 24VAC transformer in 

a star topology. The transformer must be installed in close proximity to 

the controller according to the cable gauge and total load.  
 

Table 1:  Maximum Number of VAV Devices on a Power Run 

(Daisy-Chained) 

AWG 

Power Run 

Total Cable 

Length 

Maximum 

Number of 

Devices @ 

7 VA per 

device

1

 

Maximum 

Number of 

Devices @ 10 

VA per device

2

 

Maximum 

Number of 

Devices@ 15 

VA per 

device

3

 

14

4

 

75M (250 feet)  4 

14

4

 

60M (200 feet)  5 

14

4

 

45M (150 feet)  5 

14

4

 

30M (100 feet)  5 

16 

60M (200 feet)  3 

16 

45M (150 feet)  5 

16 

30M (100 feet)  5 

18 

45M (150 feet)  3 

18 

30M (100 feet)  5 

1.  Typical VAV with 1 Allure Series Communicating Sensor (without 

CO2 sensor) and actuator activated. No external loads. 

2.  Typical VAV with 1 Allure Series Communicating Sensor (without 

CO2 sensor), 2 triac loads (1.6 VA each), 1 analog output (20 mA), 

and actuator activated. 

3.  Typical VAV with 1 Allure Series Communicating Sensor (without 

CO2 sensor), 4 triac loads (1.6 VA each), 2 analog outputs (20 mA 

each), and actuator activated 

OR 

Typical VAV with 1 Allure Series Communicating Sensor with CO2 

sensor, 2 triac loads (1.6 VA each), 1 analog output (20 mA), and 

actuator activated. 

4.  Device terminals are not capable of accepting two 14 AWG wires 

(when daisy-chaining devices). Use a wire nut with a pig tail to 

make such a connection. 

Use an external fuse on the 24VAC side (secondary side) of the 

transformer, as shown in Figure  8, to protect all controllers against 

power line spikes. 
Maintain consistent polarity when connecting controllers and devices to 

the transformer. That is, the COM terminal of each controller and each 

peripheral should be connected to the same terminal on the secondary 

side of the transformer. 

 

The COM terminals of the controller are internally wired to 

the 24V COM terminal of the power supply. Connecting a 

peripheral or another controller to the same transformer 

without maintaining polarity between these devices will 

cause a short circuit. 

 

 

Controller 2 

      

Transformer

Controller 1 

AC

24V AC

24V COM

Fuse: 4 A Max.

Fast Acting

24 VAC

OPTIONAL: Connect to 

Electrical System Ground - 

At Power Supply Only

24V AC

24V COM

 

Figure 8:  

Power wiring 

 

Connecting the power source to Electrical System Ground 

is not a requirement for proper system operation. However 

it is good installation practice to do so in order to maintain 

the same potential between all  controllers and Protective 

Earth. 

Jumper Identification and Configuration 

Controllers have the following onsite configurable jumpers. 

Digital Outputs (DO)

Power Source

Net to Subnet Port Settings

* Factory-default positions

Subnet 

Port

Wireless 

Port

Jumpers for 

DO1 & DO2

Jumpers for 

DO3 & DO4

Triac Internal 

Power*

Triac External 

Powered

Typical locations

: Quantity may vary according to controller model

Disabled*

Enabled

 

Figure 9:  

ECL-VAV Series and ECL-103 Controller Jumper 

Locations 

 

Содержание ECL-103

Страница 1: ...ure during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged controllers Avoid areas where corroding deteriorating...

Страница 2: ...3 wire voltage and current inputs and outputs as well as triac outputs should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires The board connectors accep...

Страница 3: ...urn the controller s shaft coupler until it touches the mechanical end stop to either the fully closed position 90 boxes or the fully open position 45 and 60 boxes 6 For 90 VAV boxes If the damper clo...

Страница 4: ...wires when daisy chaining devices Use a wire nut with a pig tail to make such a connection Use an external fuse on the 24VAC side secondary side of the transformer as shown in Figure 8 to protect all...

Страница 5: ...COM To Analog To Digital Converter Potentiometer 10k 0 to 20mA input used with a 2 wire 0 to 20mA sensor powered by the controller s internal 15VDC power supply Sensor 0 20mA UIx COM 15VDC To Control...

Страница 6: ...UOx COM Linear 0 to 10VDC digital to analog output UOx 0 10V Common From Digital To Analog Output UOx COM 0 to 10VDC voltage output controlling an analog actuator that is powered by an external 24VAC...

Страница 7: ...network topology and wire length restrictions refer to the Network Guide It can be downloaded from our website It is important to use proper network terminators depending on the type of network topolo...

Страница 8: ...evices are not to be thrown away in municipal waste Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive North American Emissions Complian...

Страница 9: ...Heating Floating Actuator LONWORKS Network Back of Allure EC Smart Vue Wireless Port beneath cover E D E D Service PIN Button BAC LON Figure 14 Typical Power and Network Connections with an Allure EC...

Страница 10: ...rcuit shows approximately 0V DC and an open circuit shows approximately 5V DC Configuration problem Using EC gfxProgram check the configuration of the input Refer to the controller s user guide for mo...

Страница 11: ...eats every 2 seconds highest priority shown first Long blink continuous 1s On 1s Off continuous The controller is unconfigured Appropriate action Commission the controller Long Long Long blink 800ms O...

Страница 12: ...VAC specialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change...

Отзывы: