H a r d w a r e   I n s t a l l a t i o n   G u i d e  

 

ECL-VAV Series & ECL-103 Controllers 

 

  

Figure 1:  

From left to right: ECL-VAV and ECL-103 

Product Description 

This document describes the hardware installation procedures for the 

Single Duct Variable Air Volume / Variable Volume Temperature 

Controllers (ECL-VAVS-O, ECL-VAVS, ECL-VAV, ECL-VVTS,  and 

ECL-VAV-N), and the 10-Point Programmable Controller (ECL-103). 
The Distech  Controls Variable Air Volume / Variable Volume 

Temperature product line is designed to control and monitor various 

types of HVAC equipment such as baseboards, single and multi-stage 

duct heaters, fans, valves, lights, etc. When connected to a Wireless 

Receiver, this product line can be used with a variety of wireless 

battery-less sensors and switches. 
The ECL-VAV model supports a range of Smart Room Control 

modules that expand the controller’s range of control to include lighting 

and shades/sunblinds with the ECx-Light and ECx-Blind series control 

modules. This controller also supports the EC-Multi-Sensor ceiling-

mounted sensor and its associated EC-Remote remote control. 
Each controller uses the  L

ON

W

ORKS

®

  technology for peer-to-peer 

communication between controllers and are L

ON

M

ARK

 certified.  

This document describes the hardware installation procedures for the 

following controllers: ECL-VAVS-O, ECL-VAVS, ECL-VAV, ECL-VVTS, 

ECL-VAV-N and ECL-103.  

 

For more information on the specific layout and functionality 

of each controller, please refer to their individual 

datasheets. 

General Installation Requirements 

For proper installation and subsequent operation of the controller, pay 

special attention to the following recommendations: 

It is recommended that the controller(s) be kept at room 

temperature for at least 24 hours before installation to allow any 

condensation that may have accumulated due to low temperature 

during shipping/storage to evaporate. 

Upon unpacking the product, inspect the contents of the carton for 

shipping damages. 

Do not install damaged controllers.

 

Avoid areas where corroding, deteriorating or explosive vapors, 

fumes or gases may be present.  

Allow for proper clearance around the controller’s enclosure, wiring 

terminals, and service pin  (see Figure  14)  to provide easy access 

for hardware configuration and maintenance, and to ventilate heat 

generated by the controller. Remember to record the 12-character 

Neuron

®

 ID located on a sticker on top of the device (shown on a 

sticker below the barcode), for later commissioning. When installed 

in an enclosure, select one that provides sufficient surface area to 

dissipate the heat generated by the controller and by any other 

devices installed in the enclosure. A metal enclosure is preferred. If 

necessary, provide active cooling for the enclosure. 

The controller’s datasheet specifies the power consumption 

(amount of heat generated), the operating temperature range, and 

other environmental conditions the controller is designed to operate 

under. 

Ensure that all equipment is installed according to local, regional, 

and national regulations.  

Do not drop the controller or subject it to physical shock. 

If the controller is used and/or installed in a manner not specified by 

Distech Controls, the functionality and the protection provided by 

the controller may be impaired. 

 

 

Any type of modification to any Distech Controls product will 

void the product’s warranty. 

 

 

Before installation of the Wireless Receiver, verify that local 

communication regulations allow the installation of wireless 

devices and available frequencies to be supported in your 

area. Refer to the Open-to-Wireless™ Solution Guide for 

more information. 

 

 

Take reasonable precautions to prevent electrostatic 

discharges to the  controller when installing, servicing or 

operating the controller. Discharge accumulated static 

electricity by touching one’s hand to a well-grounded object 

before working with the controller. 

Содержание ECL-103

Страница 1: ...ure during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged controllers Avoid areas where corroding deteriorating...

Страница 2: ...3 wire voltage and current inputs and outputs as well as triac outputs should be kept apart from other types of wiring to avoid any ambient noise transmission to other wires The board connectors accep...

Страница 3: ...urn the controller s shaft coupler until it touches the mechanical end stop to either the fully closed position 90 boxes or the fully open position 45 and 60 boxes 6 For 90 VAV boxes If the damper clo...

Страница 4: ...wires when daisy chaining devices Use a wire nut with a pig tail to make such a connection Use an external fuse on the 24VAC side secondary side of the transformer as shown in Figure 8 to protect all...

Страница 5: ...COM To Analog To Digital Converter Potentiometer 10k 0 to 20mA input used with a 2 wire 0 to 20mA sensor powered by the controller s internal 15VDC power supply Sensor 0 20mA UIx COM 15VDC To Control...

Страница 6: ...UOx COM Linear 0 to 10VDC digital to analog output UOx 0 10V Common From Digital To Analog Output UOx COM 0 to 10VDC voltage output controlling an analog actuator that is powered by an external 24VAC...

Страница 7: ...network topology and wire length restrictions refer to the Network Guide It can be downloaded from our website It is important to use proper network terminators depending on the type of network topolo...

Страница 8: ...evices are not to be thrown away in municipal waste Products must be disposed of at the end of their useful life according to local regulations and the WEEE Directive North American Emissions Complian...

Страница 9: ...Heating Floating Actuator LONWORKS Network Back of Allure EC Smart Vue Wireless Port beneath cover E D E D Service PIN Button BAC LON Figure 14 Typical Power and Network Connections with an Allure EC...

Страница 10: ...rcuit shows approximately 0V DC and an open circuit shows approximately 5V DC Configuration problem Using EC gfxProgram check the configuration of the input Refer to the controller s user guide for mo...

Страница 11: ...eats every 2 seconds highest priority shown first Long blink continuous 1s On 1s Off continuous The controller is unconfigured Appropriate action Commission the controller Long Long Long blink 800ms O...

Страница 12: ...VAC specialist installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail safe environments Distech Controls reserves the right to change...

Отзывы: