ESIM022 User manual v1.1
8. INPUTS
The system comes equipped with 2 inputs identified as Z1 and Z2. Depending on the input
and selected mode, the inputs are designed for different detection device connection, such as
motion detectors, door contacts, temperature sensors etc. (see
8.1. Input Z1
and
8.2. Input
Z2
). Once the detection device is triggered, the system will send a notification to the user phone
number (see
10. ALARM/RESTORE NOTIFICATIONS)
.
8.1. Input Z1
Input Z1 operates in Digital mode. The system monitors the input voltage resulting in the input
state change. Normally, this input is used for for PGM output connection of non-GSM alarm
system, motion detectors, door contacts and other passive or active digital level sensors.
The system follows this pattern for input Z1:
a) Monitors input voltage ranging from 0 mV through 3000 mV every 100 millisecond.
b) Verifies if the set up threshold (by default – 1500 mV) is not exceeded.
c) By default, the input is set as NO (normally open), therefore if the voltage drops below
the threshold, it will result in input state change to alarm followed by notifying the user
by SMS text message and/or phone call.
d) When the voltage rises above the threshold, it will result in input state change to restore
followed by notifying the user by SMS text message or phone call (only for alarm state).
Set threshold
SMS
SMS text message content:
Z1VLEV:vthr
Value:
vthr
– threshold, range - [0... 3000] mV
Example:
Z1VLEV:2350
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
Set input as NC
(normally closed)
SMS
SMS text message content:
ZONE1:NC
Example:
ZONE1:NC
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.