7
PHRVR 305
Introducing the PHRVR 305 series of Heat Recovery
Ventilators (HRV) by Powrmatic. As with previous designs,
incoming fresh outdoor air is filtered before it is heated by
the stale outgoing air. The HRV then distributes the
preheated fresh filtered air throughout the home by direct
ductwork installed specifically for the HRV or through the
ductwork of a forced-air system.
NEW FEATURES:
• Balancing Dampers Included In Installation Kit
(not factory installed
)
• Electrostatic Filters (washable)
• External Screw Type Dry Contacts For Push Button
Timers (RTS 2), Dehumidistats 1, Dehumidistat 2
& 5MR Intellitek control
OPTIONAL CONTROLS
• 5MR
– Digital Multi-Function Control
• DEH. 2 – Mechanical Low Voltage Dehumidistat with
On/Off Switch
• DEH. 1 – Mechanical Low Voltage Dehumidistat
• RTS 2 – 15 Minute Push Button Timer
• AQS 1 – Air Quality Sensor
External screw type dry contacts (provided)
SPECIFICATIONS
CASE
22 gauge galvanized steel. Baked powder coated paint,
grey. Insulated with 1" (25 mm) high density polystyrene
foam to prevent condensation and meet the requirements of
the Underwriters Laboratories 94HB.
MOTORS
Two (2) German-manufactured, factory-balanced
ebm™ motors with backward curved blades. Motors come
with permanently lubricated sealed bearings guarantee long
life and maintenance-free operation. Seven (7) year warranty.
CORES
Two (2) polypropylene heat recovery cores configured
for an efficient cross-flow ventilation. Core is 12" x 12" (305
x 305 mm) with a 15" (380 mm) depth. Cores are
manufactured to withstand extreme temperature variations.
FILTERS
Two (2) synthetic high quality filters for better indoor
air quality and clean air.
CONTROLS
External three (3) position (Low/Stand By/
Medium) rocker switch that will offer continuous ventilation.
Powrmatic offers a variety of external controls.
(see optional controls)
DEFROST
A preset 5 minute defrost sequence is activated at
an outdoor air temperature of 23ÞF (-5ÞC) and lower.
During the PHRVR 305 defrost sequence, its mechanism
uses a motorized damper to temporarily block the incoming
fresh air stream allowing the warm air from the home to
circulate through the HRV. The exhaust blower shuts down &
the supply blower switches into high speed to maximize the
effectiveness of the defrost strategy.
The unit then returns to normal operation for 25 minutes,
and continues cycle.
SERVICEABILITY
Core, filters, motors and drain pan can be
easily serviced through latched access door.
Powrmatic, reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position.
Содержание PHRV 140